Installation & Operation Manual - Model AVC5000
Contents of this Manual are Subject to Change Without Notification
Page 53
Obj.I.D.
Description
PV
Units
DExxx
Device Object
x
AI1
Airflow Volume
R
Volume
Note 2
AI2
Analog Airflow Volume Setpoint
R
Volume
AI3
Valve Position Feedback
R
%
Note 1
AI4
Face Velocity
R
Velocity
Note 1
AI5
Face Velocity Set point
R
Velocity
Note 1
AI6
Sash Position %
R
%
AI7
Flash Writes Remaining
R
AI8
Effective Airflow Volume Setpoint
R
Volume
Note 4
AV1
BACnet Airflow Volume Setpoint
W
Volume
AV2
Unsubscribed COV Interval
W
Seconds
Note 3
AV3
Airflow Volume Setpoint Offset
W
Volume
AV4
Airflow Volume Measurement Adjust
W
%
Note 6
AV5
Airflow Volume Setpoint Minimum Limit
W
Volume
Note 6
AV6
Airflow Volume Setpoint Maximum Limit
W
Volume
AO1
Valve Actuator Command Position
C
%
BI1
Alarm: 0=normal, 1=alarm
R
Note 1
BI2
Low Face Velocity Alarm Status: 0=normal, 1=alarm
R
Note 1
BI3
Low Volume Alarm Status: 0=normal, 1=alarm
R
Note 1
BI4
Sash Position Alarm Status: 0=normal, 1=alarm
R
Note 1
BI5
Emergency (Purge) Status: 0=normal, 1=purge
R
Note 1
BV1
Remote Purge Request: 0=normal, 1=purge
W
Note 5
BV2
Write to Flash
W
Note 1
BV3
BACnet Digital1 Condition
W
Binary
Note 1
BV4
BACnet Digital2 Condition
W
Binary
MSI1
DI states 1..4
R
MSI2
Mode Selector: 1=AI2, 2=MSI1, 3=AV1, 4=FumeHood, 5=Hibernate
R
MSI3
Airflow Volume Units: 1=CFM, 2=CMS, 3=CMM,4=CMH, 5=LPS, 6=LPM
W
Note 1
MSI4
Face Velocity Units: 1=FPM, 2=MPM, 3=MPS
W
Note 1:
These objects are only valid when operating in Fume Hood Mode (MSI2=4).
Note 2:
This object is only valid when operating in Setpoint Mode (MSI2=1)
Note 3
: This object is NOT valid when operating in either Fume Hood Mode (MSI2=4) or Hibernate Mode (MSI2=5)
Note 4:
This object is only valid when operating in BACnet Mode (MSI2=3)
Note 5
: Save active configuration to Nonvolatile Flash memory. Please review section 7.1.1 for further information.
Writing a value of one (1) to the BACnet Object BV2 will cause the controller to copy the active
configuration stored in volatile (RAM) memory and write it to nonvolatile Flash memory. Nonvolatile Flash
memory has a limited number of Lifetime Write Cycles. Use this feature only when necessary.
Note 6
: This object is only valid when operating in Setpoint Mode where physical input AI1 is controlling Setpoint
The AVC control module includes a USB port which provides local connectivity for
programing the AVC using the PC based software tool “Insight” described in Section 6.
For BACnet operation, the PC must be disconnected from the local USB port to avoid
conflicts.