Installation & Operation Manual - Model AVC5000
Contents of this Manual are Subject to Change Without Notification
Page 38
6.6.4.2.5.9 Examples of How to Configure Alarms
There are many different alarms and alarm parameters available, however the same basic
configuration steps are similar therefore only two examples have been provided below.
Example 1
Control Configuration =
No Setback, Digital Inputs are Not Used
Alarm Configuration =
Enable Low/High Face Velocity Alarm, Other Alarms Disabled
Note:
Time delays are used to eliminate false triggering and nuisance alarms.
Alarm Sequence for Example 1
Face Velocity = 100 FPM
No Active Alarms; Low Velocity Alarm = Normal State
Face Velocity drops below 60 FPM
6 seconds after Face Velocity is drops below 60 FPM, the Low
Velocity Alarm will enter into its Alarm State
Face Velocity increases above 60 FPM
12 seconds after Face Velocity goes above 60 FPM, the Low
Velocity Alarm will return to its Normal State
Save
Changes
Enable
Enter Alarm
In/Out Time
Delay
Enter Face
Velocity
Alarm Values
Check
Enable
Select Status
Indicator
Color
Select