SECTION 2
–
SPECIFICATIONS
PERFORMANCE
Accuracy
+/- 5% of reading or 5 CFM, whichever is greater
Speed of Response
< 1 second control signal response (full stroke cycle time is 10 seconds)
Shut-off Leakage Rate
Standard: < 1.5% FS at max operating pressure
"S" Option: < 0.5% FS round valves, < 1% FS rectangular valves @ max operating pressure
Max Operating Pressure
3”wc Differential Pressure Across Valve
Min Operating Pressure
Reference Section 2.1
Airflow Range
Reference Section 2.1
Failure Mode
Last Position
ENVIRONMENTAL
Temperature
Airstream: -20 to 165 deg. F for all Standard Valve Models
Ambient: -20 to 125 deg. F Storage: -40 to 165 deg. F
Humidity
0 to 90% non-condensing
ELECTRICAL
Power:
24VAC +/- 20% 50/60Hz. (Class 2 Power Source) 17VA
24VDC +/- 10%, 9W
Analog Input: Software Selectable:
Voltage, Current or Resistance
Voltage: 0-10v Range, Input Impedance = 100K ohms
Current: 0-20mA Range, Input Impedance = 500 ohms
Resistance: 0-20K Range, 500uA Internal Current Source
Digital Inputs:
2 dry-contact inputs
Analog Output:
Software Selectable:
0-20mA, 4-20mA, 0-10V, 2-10V, 0-5V or 1-5V
V-out capable of driving 1 K-ohm load @ 10V, I-out capable of driving 1K-ohm load
RS-485:
EIA 485 BACnet MS/TP 2-wire, Receiver Impedance: ¼ unit load
Note: Network bias and field termination are NOT provided by the AVC Control Module
Configuration Port:
USB Type C, Wireless Bluetooth (Optional)
Power:
2-Position, vertical pluggable, Wire Size range - 18-30 AWG
IO:
7-Position terminal block, Wire size range - 16-30 AWG
BACnet:
2-Position terminal block, Wire size range - 16-30 AWG
Compliance
, RoHS, BTL Listed
Electromagnetic
Compatibility
2014/30/EU, EMC Directive
EN61236-1:2013
2014/53/EU, Radio Equipment Directive
EN301489-1, V1.9.2:2011
ETSI EN301489-1, V2.2.0:2017
ETSI EN301489-3, V1.6.1:2013/V2.1.1:2017
ETSI EN301489-17, V2.2.1:2012/V3.2.0:2017
Product Safety
2014/35/EU, Low Voltage Directive
EN61010-1:2010/A1:2019/AC:2019