Installation & Operation Manual - Model AVC4000
Contents of this Manual are Subject to Change Without Notification
Page 22
6.5.5 Analog Output Gauge
The Analog Output Gauge is provided for indicating the status and configuration of the Analog
Output. The
Analog Output Configuration Menu is provided by selecting the “CONFIG” button.
6.5.5.1 Analog Output Configuration
S
electing the “
CONFIG
” button on the
Analog Output Gauge will open a window that will enable
you to enter the configuration parameters available for that Analog Output. The examples
provided below explain the parameters available and how to configure each.
Output Source Selected:
MEASURED AIRFLOW
sets the AO to
correspond with the measured
airflow volume.
Output Full Scale: Provides the full-scale range of the
AO and the corresponding AO
Gauge, which is 850 cfm for this
example.
Output Signal Type: Select from dropdown list. For this
example, 10v corresponds to 850
cfm.
Filter: Increasing the filter will smooth out
the reading, however it also slows
down the response, therefore it
should be used with caution.
Output Source Selected:
VALVE % OPEN
sets the AO to
correspond with the valve % open
value.
Output Full Scale: Provides the full-scale range of the
AO Signal and the corresponding AO
Gauge.
Output Signal Type: Select from dropdown list. For this
example, 10v corresponds to 100 %
open.
Select “CONFIG” to Open
Configuration Window
Analog Output Full Scale
Output Value Indicator
Present Analog Output Configuration
Output Value Indicator
Analog Output
Corresponding to Gauge
Parameter or Source