![Accutrol AccuValve AVC4000 Installation & Operation Manual Download Page 15](http://html1.mh-extra.com/html/accutrol/accuvalve-avc4000/accuvalve-avc4000_installation-and-operation-manual_3854548015.webp)
Installation & Operation Manual - Model AVC4000
Contents of this Manual are Subject to Change Without Notification
Page 15
SECTION 5
–
WIRING
5.1 AVC4000 Control Module
CONTROL MODULE
Alternate Cable Entry
24 Gauge Galvanized
Steel Cover
NOTE: If a conduit
connection is required,
the strain relief fitting
and bushing can be
removed and replaced
with a .875" (22mm)
conduit fitting.
(Provided by Others)
WARNING: Do not use
controller enclosure as
junction box for other
equipment
2.
Route cables through the strain-
relief fitting into the enclosure.
3.
Connect wires to the appropriate
terminals.
4.
Secure terminal screws.
5.
Insert the ratcheting strain relief over
cable(s) and push down until snug.
6.
Reinstall cover.
Wiring
Instructions
1.
Remove cover.
Bluetooth Antenna
(-W Option Only)
5.2 Control Module Wiring Diagram:
Connections will vary based on application.
SW 1
NOTE: Connections will vary based on
application. For detailed wiring instructions, use
this drawing in conjunction with the job-specific
wiring diagrams.
OR
Power Source
24 vAC
24 vDC
DDC
Controller
SW 2
Analog
Output
Analog
Input
MS/TP
BACnet
EIA 485
BACnet
MS/TP Bus
From
Previous
Device
To Next
Device
Shield
Optional Wireless Bluetooth Module
Reference Wireless Bluetooth Field Manual.
NOTE:
Switch or circuit
breaker must be
included in the
installation
located where it
is easily reached
and marked as
disconnecting
device for the
equipment.
Power source must
be current limited to
less than 8 amps.
CAUTION:
Maintain polarity if power source is used for multiple devices, otherwise
equipment may be damaged.