11
Main interface
T01
Cabinet internal temp-
erature
T02
Evaporator temperature
T03
Condenser temperature
T04
Cabinet internal humidity
E01
Cabinet internal high
temperature alarm
E02
Cabinet internal low
temperature alarm
E03
Cabinet internal tempErature
sensor alarm
E04
Evaporator tempErature
sensor alarm
E05
Condenser tempErature
sensor Alarm
E06
Evaporator- frozen alarm
E07
System high pressure alarm
P01
Refrigeration starting temperature setting
Size:
25
~
45
P02
Refrigeration return difference
setting
Size:
3
~
10
P03
High temperature alarm setting
Size:
25
~
45
P04
Low temperature alarm setting
Size:
30
~
60
P05
Heating starting temperature setting
Size:-30
~
15
P06
Heating
return difference
setting
Size:5
~
15
P07
Communication address setting
Size:
0
~
255
Code input interface
(User
:
001
)
Definition
Icon
Definition
Icon
Icon
Definition
5.3
Display
Under running, the main interface
8.8.8
displays real temperature value in cabinet
After boot, in any interface, if there has no keyboard operation in the continuous 60s,
automatically return to the main interface
5.4
Start
self-test
In the running states, the self-checking function can be activated by continuous pressing
SET
for 3
seconds.
When Self-check, the screen will be full display for 1S, and then will normally display cabinet
temperature, while the boot icon will blink.
6
Running
6.1
Check before start running
1)
There are not obvious blockages near the internal cycle air inlet and outlet of the
air conditioner.
2)
The input power cables and other signal cables have been connected reliably
and correctly.