9
Hydrogen discharge function(Optional)
:
When hydrogen discharge cycle comes, air conditioner start
the hydrogen discharge fan, the control switch closes.
hydrogen discharging function
parameter
Default value
Setting range
Unit
cycle
24
[0
~
72]
h
discharging time
5
[0
~
10]
Min
Emergency ventilation function (Optional): When the temperature inside cabinet is higher than
Emergency ventilation starting temperature, emergency ventilation fans run; when the temperature inside
cabinet is lower than Emergency ventilation stopping temperature, emergency ventilation fans stop.
Emergency ventilation function
parameter
Default value
Setting range
Unit
starting temperature
45
[28
~
50]
℃
stopping temperature
42
[25
~
50]
℃
5
Display screen
5.1
Display interface
NO.
Icon
Function
Function explanation
1
Refrigerating
running
Indicate whether refrigerating runs or not
2
Heater running Indicate whether heater runs or not
3
Fan running
Indicate whether fan runs or not
Summary of Contents for MGA0800/A1