Commissioning
4.5.6
Network Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
Network Protocol
0 Not Active
This parameter will only display
the selection for the module that is
installed.
Remote Keypad
2 Modbus RTU
CANopen
4 DeviceNet
5 Ethernet
Profibus
…
Module Specific Parameters
Refer to the Reference Guide specific
to the module installed.
4.5.7
Diagnostic Parameters
Code
Display Range
(READ ONLY)
IMPORTANT
No.
Name
Fault History
• Displays the last 8 faults
• Format: n.xxx
where: n = ..8;
is the newest fault
xxx = fault message (without the
.
)
• see Section 5.
Software version
Format: x.yz
Drive ID
A flashing display indicates that the Drive ID
stored in the EPM does not match the drive
model it is plugged into.
Internal Code
Alternating Display: xxx-; -yy
DC Bus Voltage
0
{VDC}
500
Motor Voltage
0
{VAC}
000
Load
0
{%}
255
Motor load as % of drive’s output current rating.
See section 2.2.
Motor Current
0.0
{A}
000 Actual motor current
Torque
0
{%}
500
Torque as % of motor rated torque
(vector mode only)
kW
0.00
{kW}
50.0
kWh
0.0
{kWh}
9999999 Alternating display: xxx-; yyyy when value
exceeds 9999
Heatsink Temp
0
{°C}
50
Heatsink temperature
0-0 VDC Input
0.0
{VDC}
0.0
Actual value of signal at TB-5
4-20 mA Input
0.0
{mA}
20.0
Actual value of signal at TB-25
TB-5 Feedback
P204
P205 TB-5 signal value scaled to PID feedback units
TB-25 Feedback P204
P205 TB-25 signal value scaled to PID feedback units