ENGLISH
22
Commissioning
4.5.3
Advanced Setup Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
Speed at
Minimum Signal
0.0
-999.0
{Hz}
000
f
P161
P160
ref
10V
(20mA)
0V
(4mA)
V0
Speed at
Maximum Signal
0.0
-999.0
{Hz}
000
Note
• P0 sets the output frequency at 0% analog input
• P sets the output frequency at 00% analog input
• P0 or P < 0.0 Hz: For scaling purposes only; does not indicate
opposite direction!
• P0 > P: Drive will react inversely to analog input signal
Analog Input
Filter
0.0
0.00
{s}
0.00
Adjusts the filter on the analog inputs
(TB-5 and TB-25) to reduce the effect
of signal noise
TB-25 Loss
Action
0
0 No Action
• Selects the reaction to a loss of the
4-20 mA signal at TB-25.
• Signal is considered lost if it falls
below 2 mA
• Digital outputs can also indicate a
loss of 4-20 mA signal; see P40,
P42
Fault
2 Go to Preset when TB-25 is:
Speed reference: P7
PID feedback source: P7
PID setpoint reference: P2
Torque reference: P
Carrier
Frequency
0 4 kHz
• As carrier frequency is increased,
motor noise is decreased
• Observe derating in Section 2.2
• Automatic shift to 4 kHz at 20%
load
kHz
2 8 kHz
0 kHz
()
Base Frequency
0.0
0.0
{Hz}
500
V02
Fixed Boost
0.0
{%}
0.0
Note
• P7 = rated motor frequency for standard applications
• P8 default setting depends on drive rating
Accel Boost
0.0
0.0
{%}
20.0
Accel Boost is only active during
acceleration
() Any changes to this parameter will not take effect until the drive is stopped