Troubleshooting and Diagnostics

5.3 

Fault Messages

The messages below show how they will appear on the display when the drive trips.  When looking at 
the Fault History (P500), the 

.

 will not appear in the fault message.

Fault

Cause

Remedy 

(1)

High Temperature fault

Drive is too hot inside

•  Reduce drive load
•  Improve cooling

Assertion Level fault

•  Assertion Level switch is 

changed during operation

•  P20 is changed during 

operation

• 

P00 or P2...P2 are set to 
a value other than 0 and P20 
does not match the Assertion 
Level Switch.

•  Make sure the Assertion Level 

switch and P20 are both set for 
the type of input devices being 
used, prior to setting P00 or 
P2...P2. 
See .2. and P20.

Personality fault

Drive Hardware 

•  Cycle Power
•  Power down and install EPM with 

valid data

•  Reset the drive back to defaults 

(P99 = , 4) and then re-
program

•  If problem persists, contact 

factory technical support

Control fault

An EPM has been installed that is 
either blank or corrupted

Incompatible EPM fault

An EPM has been installed that 
contains data from an incompatible 
parameter version 

Dynamic Braking fault

Dynamic braking resistors are 
overheating

•  Increase active decel time 

(P05, P2, P27).

•  Check mains voltage and P07

External fault

•  P2…P2 = 2 and that digital 

input has been opened.

•  P2…P2 = 22 and that digital 

input has been closed.

•  Correct the external fault 

condition

•  Make sure digital input is set 

properly for NC or NO circuit

EPM fault

EPM missing or defective

Power down and replace EPM

 

Internal faults

Contact factory technical support

Invalid message received •  A network message was 

received while in Remote Keypad 
mode

•  A remote keypad message was 

received while in Network mode

Only the remote keypad or the 
network can be connected at one 
time; see P00

Loss of 4-20 mA signal 
fault

4-20 mA signal (at TB-25) is below 
2 mA (P = )

Check signal/signal wire

OEM Defaults data fault

Drive is powered up with  
P99 = and OEM settings in the 
EPM are not valid.

Install an EPM containing valid 
OEM Defaults data or change P99 
to 0.

High DC Bus Voltage 
fault

Mains voltage is too high

Check mains voltage and P07

Decel time is too short, or too much 
regen from motor

Increase active decel time  
(P05, P2, P27) or install 
Dynamic Braking option

() The drive can only be restarted if the error message has been reset

Summary of Contents for Lenze SV01B

Page 1: ...V0100 SV01B Operating Instructions SMVector frequency inverter 0 5 10 HP 0 37 kW 7 5 kW...

Page 2: ...t accept any responsibility nor liability for damages that may occur Any necessary corrections will be implemented in subsequent editions This document printed in the United States 1 Safety informatio...

Page 3: ...For detailed information refer to instruction Manual SV01 000000000000000000 ESV751N04TXB000XX V0101 E Hardware Version F Software Version 1 SMV inverter ESV Lenze AC Tech Lenze AC Tech representative...

Page 4: ...tion into a machine or process It is neither a machine nor a device ready for use in accordance with European directives reference machinery directive and electromagnetic compatibility directive It is...

Page 5: ...warnings are notes which apply to UL systems The documentation contains special information about UL Warnings Suitable for use on a circuit capable of delivering not more than 200 000 rms symmetrical...

Page 6: ...g Temperature range Transport 25 70 C Storage 20 70 C Operation 10 55 C with 2 5 C current derating above 40 C Installation height 0 4000m a m s l with 5 1000 m current derating above 1000m a m s l Vi...

Page 7: ...0 75 16 6 8 3 4 2 200 52 240VAC Models Type Power Hp kW Mains Output Current Watts Loss Voltage 1 Iin 1 2 PE Iin 3 3 PE In CLimmax 2 0 33 0 25 240 V Single Phase 2 PE 3 4 1 7 200 20 0 5 0 37 240 V Si...

Page 8: ...0 3 5 175 200 57 3 2 2 6 1 5 4 5 5 4 8 175 200 87 5 4 0 10 6 9 3 9 4 8 2 175 200 128 7 5 5 5 14 2 12 4 12 6 11 0 175 200 178 10 7 5 18 1 15 8 16 1 14 0 175 200 208 600VAC Models Type Power Hp kW Mains...

Page 9: ...for more information Installation 3 Installation 3 1 Dimensions and mounting b1 a1 a b c b2 4 X 10 18 lb in 4 X M5 20 Nm s1 s1 s2 s2 V0102 Type a in mm a1 in mm b in mm b1 in mm b2 in mm c in mm s1 in...

Page 10: ...t at least three minutes before servicing the drive STOP Verify mains voltage before connecting to drive Do not connect mains power to the output terminals U V W Severe damage to the drive will result...

Page 11: ...L3 3 2 1 4 Motor Connection U T1 V T2 W T3 PE PES PES M 3 PE PES PES PES PE PES Protective Earth Shielding Mains and Motor Terminations 12 lb in 1 3 Nm 0 25 in 6mm WARNING Leakage current may exceed...

Page 12: ...2 5 12 M25 A C25 A 25 A 2 5 12 M32 A C32A 32 A 4 10 240V 3 3 PE M10 A C10 A 10 A 1 5 14 M12 A C12 A 12 A 1 5 14 M20 A C20 A 20 A 2 5 12 M32 A C32 A 32 A 4 0 10 M35 A C35 A 35 A 6 0 8 M45 A C45 A 45 A...

Page 13: ...elay output Configurable with P140 AC 250 V 3 A DC 24 V 2 A 240 V 0 22 A non inductive 17 6 25 4 11 13A13B13C 17 5 1 2 14 30 16 AOUT DIGOUT 2k 10k 10 V AIN AIN COM COM ALsw 25 2 4 20 mA 5 2 0 10 V 0 5...

Page 14: ...D will blink until the drive is controlling the motor in the selected direction MODE Used to enter exit the Parameter Menu when programming the drive and to enter a changed parameter value UP AND DOWN...

Page 15: ...the User settings in the EPM An optional EPM Programmer model EEPM1RA is available that allows An EPM to be copied directly to another EPM An EPM to be copied to the memory of the EPM Programmer Stor...

Page 16: ...control to be switched between terminal strip and optional remote keypad using one of the TB 13 inputs See note below WARNING P100 0 disables TB 1 as a STOP input STOP circuitry may be disabled if pa...

Page 17: ...ue increasing P103 WARNING Consult motor machine manufacturer before operating above rated frequency Overspeeding the motor machine may cause damage to equipment and injury to personnel Acceleration T...

Page 18: ...t will occur if start command is applied too soon P110 1 3 6 For automatic start restart the start source must be the terminal strip and the start command must be present P110 2 4 6 If P175 999 9 dc b...

Page 19: ...OP Down 6 AUTO Reference Keypad 7 AUTO Reference Network 8 Control Select Use when P100 4 5 to switch between terminal strip control and local or remote keypad control 9 Network Enable Required to sta...

Page 20: ...P Up and another is not set to MOP Down or vice versa One input is set to 10 and another input is set to 11 14 One input is set to 11 or 12 and another input is set for 13 or 14 Typical control circui...

Page 21: ...ce is active for start control 12 Terminal Strip Control Active 13 Remote Keypad Control Active 14 Network Control Active 15 Standard Reference Active Energizes when P101 reference is active 16 Auto R...

Page 22: ...500 W 1 0 10 VDC Output Frequency 2 2 10 VDC Output Frequency 3 0 10 VDC Load 4 2 10 VDC Load 5 0 10 VDC Torque 6 2 10 VDC Torque 7 0 10 VDC Power kW 8 2 10 VDC Power kW 9 Network Controlled Requires...

Page 23: ...on 0 0 No Action Selects the reaction to a loss of the 4 20 mA signal at TB 25 Signal is considered lost if it falls below 2 mA Digital outputs can also indicate a loss of 4 20 mA signal see P140 P142...

Page 24: ...ill be applied for 15s If P121 P123 18 and the corresponding TB 13 input is CLOSED brake voltage will be applied until the TB 13 input is OPENED or a fault condition occurs Display Frequency Multiplie...

Page 25: ...Check P100 and P121 P123 Note 1 If the EPM does not contain valid OEM settings a flashing GF will be displayed when P199 is set to 1 or 2 Note 2 When P199 is set to 1 the drive operates from the OEM...

Page 26: ...feedback signal 1 0 10 VDC TB 5 PID Decimal Point 1 0 PID Display XXXX Applies to P204 P205 P214 P215 P231 P233 P242 P522 P523 1 PID Display XXX X 2 PID Display XX XX 3 PID Display X XXX 4 PID Display...

Page 27: ...reset PID Setpoint 3 0 0 P204 P205 TB 13C activated P123 3 and P200 1 or 2 Sleep Threshold 0 0 0 0 Hz 500 0 If drive speed P240 for longer than P241 output frequency 0 0 Hz drive display P240 0 0 Slee...

Page 28: ...Set P302 P306 according to motor nameplate Set P399 1 Make sure motor is cold 20 25 C and apply a Start command Display will indicate for about 40 seconds Once the calibration is complete the display...

Page 29: ...ect performance Contact factory technical support prior to changing 1 Current Loop I Gain 65 12 ms 9990 1 Speed Loop Adjustment 0 0 0 0 20 0 Motor Auto calibration 0 0 Calibration Not Done If P300 2 5...

Page 30: ...n Format x yz Drive ID A flashing display indicates that the Drive ID stored in the EPM does not match the drive model it is plugged into Internal Code Alternating Display xxx yy DC Bus Voltage 0 VDC...

Page 31: ...n Time 0 h 9999999 4 5 7 1 Terminal and Protection Status Display Parameter P530 allows monitoring of the control terminal points and common drive conditions An illuminated LED segment indicates the p...

Page 32: ...ease P171 Verify drive motor are proper size for application Decel Override The drive has stopped decelerating to avoid tripping into fault due to excessive motor regen 2 sec max If drive trips into f...

Page 33: ...4 digit code that indicates how the drive is configured If the drive is in a Stop state when this is done the display will also indicate which control source commanded the drive to Stop the two displa...

Page 34: ...le parameter version Dynamic Braking fault Dynamic braking resistors are overheating Increase active decel time P105 P126 P127 Check mains voltage and P107 External fault P121 P123 21 and that digital...

Page 35: ...empt was made to start the drive in Vector or Enhanced V Hz mode prior to performing the Motor Auto calibration See P300 P399 for Drive Mode setup and calibration Module communication fault Communicat...

Page 36: ...Controller was unable to synchronize with the motor during restart attempt P110 5 or 6 Check motor load Single Phase fault A mains phase has been lost Check mains voltage Start fault Start command was...

Page 37: ...Notes...

Page 38: ...AC Technology Corporation 630 Douglas Street Uxbridge MA 01569 USA 1 508 278 9100 SV01B...

Reviews: