ENGLISH
Troubleshooting and Diagnostics
5.3
Fault Messages
The messages below show how they will appear on the display when the drive trips. When looking at
the Fault History (P500), the
.
will not appear in the fault message.
Fault
Cause
Remedy
(1)
High Temperature fault
Drive is too hot inside
• Reduce drive load
• Improve cooling
Assertion Level fault
• Assertion Level switch is
changed during operation
• P20 is changed during
operation
•
P00 or P2...P2 are set to
a value other than 0 and P20
does not match the Assertion
Level Switch.
• Make sure the Assertion Level
switch and P20 are both set for
the type of input devices being
used, prior to setting P00 or
P2...P2.
See .2. and P20.
Personality fault
Drive Hardware
• Cycle Power
• Power down and install EPM with
valid data
• Reset the drive back to defaults
(P99 = , 4) and then re-
program
• If problem persists, contact
factory technical support
Control fault
An EPM has been installed that is
either blank or corrupted
Incompatible EPM fault
An EPM has been installed that
contains data from an incompatible
parameter version
Dynamic Braking fault
Dynamic braking resistors are
overheating
• Increase active decel time
(P05, P2, P27).
• Check mains voltage and P07
External fault
• P2…P2 = 2 and that digital
input has been opened.
• P2…P2 = 22 and that digital
input has been closed.
• Correct the external fault
condition
• Make sure digital input is set
properly for NC or NO circuit
EPM fault
EPM missing or defective
Power down and replace EPM
Internal faults
Contact factory technical support
Invalid message received • A network message was
received while in Remote Keypad
mode
• A remote keypad message was
received while in Network mode
Only the remote keypad or the
network can be connected at one
time; see P00
Loss of 4-20 mA signal
fault
4-20 mA signal (at TB-25) is below
2 mA (P = )
Check signal/signal wire
OEM Defaults data fault
Drive is powered up with
P99 = and OEM settings in the
EPM are not valid.
Install an EPM containing valid
OEM Defaults data or change P99
to 0.
High DC Bus Voltage
fault
Mains voltage is too high
Check mains voltage and P07
Decel time is too short, or too much
regen from motor
Increase active decel time
(P05, P2, P27) or install
Dynamic Braking option
() The drive can only be restarted if the error message has been reset