ENGLISH
2
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
TB-4 Output
0
0...2 (same as P40)
24 Dynamic Braking
For use with Dynamic Braking option
25 Network Activated
Requires optional communication
module (refer to the network module
documentation).
Loss of Load
Threshold
0
0
{%}
200
P40, P42 = 0: Output will energize
if motor load falls below P45 value
longer than P4 time
Loss of Load
Delay
0.0
0.0
{s}
240.0
TB-0 Output
0
0 None
2-0 VDC signal can be converted to
4-20 mA with a total circuit impedance
of 500
W
0-0 VDC Output Frequency
2 2-0 VDC Output Frequency
0-0 VDC Load
4 2-0 VDC Load
5 0-0 VDC Torque
2-0 VDC Torque
7 0-0 VDC Power (kW)
8 2-0 VDC Power (kW)
9 Network Controlled
Requires optional communication
module (refer to the network module
documentation).
TB-0 Scaling:
Frequency
0.0
.0
{Hz}
2000
If P50 = or 2, sets the frequency at
which output equals 0 VDC
TB-0 Scaling:
Load
200
0
{%}
500
If P50 = or 4, sets the Load (as a
percent of drive current rating) at which
output equals 0 VDC.
TB-0 Scaling:
Torque
00
0
{%}
000
If P50 = 5 or , sets the Torque (as a
percent of motor rated torque) at which
output equals 0 VDC
TB-0 Scaling:
Power (kW)
.0
0.
{kW}
200.0
If P50 = 7 or 8, sets the power at
which output equals 0 VDC