Page 14
Data : 01.03.2016
8
Activation of LIS control unit
Important: Once the load measurement and evaluation
function has been activated, it cannot be deactivated
again.
To activate the load measurement and evaluation func-
tion of the LIS control unit, select parameter 3.0 using
the ”up” button. Press the ”enter” button for some time
and the system will request you to enter a PIN no. Enter
”0055”. Press ”enter” again. The unit will be re- initiali-
zed and activation will be completed.
_________________________________
9
Disposal
ABUS products are designed with a view to recycling
and have a modular structure which facilitates environ-
mentally compatible disposal when they are no longer
required.
The electronic components may be disposed of at spe-
cial disposal sites in accordance with the applicable lo-
cal regulations.
_________________________________
10
LIS – SE parameter list
Para-
meter
Range
Unit
Designation
Remarks
CodE
Reading out load population recorder
“Menu level 1”
Only available if LKS has
been enabled.
CODE 2223
P 0.0
0 – 100
t
Total load capacity
Input not required
P 0.1
0 – 80
t
Display and input
Load capacity, hoist 1
P 1.1
0 – 17
Display and input
Motor type
in accordance with table
P 1.2
0–97,999
Display and input
Winding resistance
P 1.3
Display and input
Current correction factor
P 2.1
Display and input
Unit setting, precision lift
P 2.2
Display and input
Unit setting, main lift
P 2.3
Unit setting t load ”Teach–in 1”
P 2.4
Unit diagnosis parameter
CODE 1443
P 3.0
t
Display mode
”Load indication”
P 3.1
kW
Display mode
”Rotating field power”
P 3.2
t
Display mode
”Load indication”
P 3.3
A
Display mode
”Conductor current”
P 3.4
V
Display mode
”Supply voltage”
P 3.41
V
Network voltage analysis
P 4.0
0–110
%
Display and input
second shut- down point
only active with signal at
input EA
P 4.1
0–110
%
Display and input
Overload shut–down, hoist 1
P 4.2
0–110
%
Display and input
Part–load switch 1
P 4.3
no function
P 4.4
Operation on twin hoist
no function