10. Maintenance and controls by the user
ACCEPTABLE WATER QUALITY LIMITS
pH (25°C)
6.8 – 8.4
Electrical conductivity (µS/cm) (25°C)
< 800
Chloride ion (mg CI
-
/I)
< 150
Chlorine molecular (mg Cl
2
/l)
< 5
Sulphate ion (mg SO
4
--
/l)
< 100
Sodium nitrate (mg NaNo
3
/I)
< 100
Alkalinity (mg CaCO
3
/1)
< 100
Total Hardness (mg CaCO
3
/1)
< 200
Iron (mg Fe/I)
< 1.0
Copper (mg Cu/I)
< 1.0
Sulphide ion (S
--
/I)
none
Ammonium ion (mg NH
4
+
/I)
< 1.0
Silica (mg SiO
2
/I)
50
Maximum particle size to pass (filtration limit) through heat exchanger (mm)
0.87
Total dissolved solids (mg/l)
< 1500
Max Ethylene, Propylene glycol
50%
construction before handling.
• Always install a filter in the water inlet circuit, in order to reduce the entry of solid particles;
• Drain totally the
vessel
before doing any maintenance operations;
• Do not clean the flooded with non-suitable mechanical systems, e.g. drills or too high pressure jets;
• Do not clean with too aggressive chemical detergents and verify their compatibility with the materials of
FOR HEAT EXCHANGERS WITH ANODES AND ANTI-CORROSION TREATMENT: IF AT
THE FIRST INSPECTION THERE IS AN EXCESSIVE CONSUPTION OF THE ANODES, IT
MEANS THAT THE ENVIRONMENT IS HIGHLY AGGRESSIVE SO IT IS NECESSARY TO
FORMULATE A “MAINTENANCE TIMETABLE” ACCORDING TO THE AGGRESSIVNESS
OF THE WATER (IT IS NOT POSSIBLE TO SUPPLY A “STANDARD” MAINTENANCE
SCHEDULE SINCE THE ANODE CONSU
M
PTION IS SUBJECT TO MANY FACTORS).
FILL COMPLETELY WITH WATER OR DRAIN TOTALLY THE
VESSEL
IN CASE OF
LONG NON-WORKING PERIODS.