EN
16
Victaulic® kits (see appendix fig. 14.2)
Victaulic® kits consist of 2 coupling connections supplied with EPDM gaskets on the inside and 2 connection
pipes.
For the installation of the kit follow the steps below:
• loosen the coupling connection and extract the gasket.
• fit the gasket between the screwed water connection of the condenser and the connection pipe, only after
you have verified the cleanliness of surfaces (it is useful to wet the gasket with water or lubricant, unless it is
incompatible with the gasket material); make sure the joint between the two pipes lies at the centre of the
gasket.
• tighten the coupling after you have verified the correct position of the gasket in order to avoid leakage.
7. Installation
7.3 Protect from vibrations
We recommend to avoid the transmission of vibrations that may cause damage to the flooded
vessel
through anti- vibrating systems.
7.4 Insulation
On request it is possible to supply an external adhesive insulation for the flooded
vessel
.
N
ormal maintenance and inspection operations are permitted.
7.6 Static electricity
Adequate precautions must be taken in order to avoid the accumulation of static electricity (according to
current local legislation).
All metallic parts of the equipment should be grounded.
7.5 Heating protection
Permanent joints of connection, obtained by welding or brazing must be made with adequate
heat protection systems; excessive exposure could damage the heat exchanger.
Flange kit
Flange kits are provided with coupling flanges, gaskets, screws and nuts.