4 Installation and Operating Instructions
Installation and Operating Instructions
ABS Control panel CP114
GB 0825-A
m
%HIRUHVWDUWLQJXSLPSRUWDQWVHWWLQJVRQWKH9)'DUHWREHPDGH9)'LVSUHFRQ¿JXUHGDFFRUGLQJWR
part-no when distributed. An examination of the parameters is urgently recommend.
0825-0003
Figure 2 Frequency converter (Fa. Schneider Electric)
A VFD of the Schneider Electric company, type Altivar ATV12 is used.
7KHPRVWLPSRUWDQWVHWWLQJVDQGRSHUDWLQJVWHSVDUHH[SODLQHGLQWKHHQFORVHGVLPSOL¿HGPDQXDO$GHWDLOHG
guideline is available on the Schneider Electric Website under
http://www.global-download.schneider-electric.com
as Download.
After connecting mains voltage and switching on the main switch, the display of the VFD shows [rdy].
The following settings are to be made and/or checked.
Menu item
Value
Comment
Main menu [COnF]
Submenu [FULL]
Menu [I_O_]
[ctd]
A
m
Threshold value for high pump
current. Activate motor protection and/
or reverse function.
Main menu [COnF]
[nCr]
A
Nominal current of pump.
Main menu [COnF]
[nPr]
kW
Nominal power of pump.
Main menu [COnF]
Submenu [FULL]
Menu [drC]
[nsP]
rpm
Nominal speed of pump.
These settings can be stored with the following function.
Menu item
Value
Comment
Main menu [COnF]
[SCS]
nO
Str 1
6WRUDJHRIWKHFXUUHQWFRQ¿JXUDWLRQ
Main menu [COnF]
[reC 1]
5HVHWVWRUHGFRQ¿JXUDWLRQ