2 Installation and Operating Instructions
Installation and Operating Instructions
ABS Control panel CP114
GB 0825-A
CP114 is a control panel for connection to a single-phase mains supply 230 V/N/PE.
m
Max. pre-fusing 16 A. If a residual-current protection device (RCD) is used, a 2-pol. universal-current-
Max. pre-fusing 16 A. If a residual-current protection device (RCD) is used, a 2-pol. universal-current-
sensitive or a super immunized RCD is recommended.
A three-phase pump 3x230 V max. IN=10 A can run on a variable frequency drive (VFD) type Altivar ATV12
(see part-no.).
Part-no.: 6216 0870 – CP114 up to 1,5 kW; 7,5 A
(Part-no. VFD 1285 0276)
Part-no.: 6216 0871 – CP114 up to 2,2 kW; 10,0 A
(Part-no. VFD 1285 0277)
,ISUREOHPVRFFXUZLWKH[LVWLQJ5&'LQVLGHLQVWDOODWLRQLQWHUQDO(0&¿OWHURIWKH9)'FDQEHGLVDEOHG7KLVFDQ
affect the EMC.
CP114 will be controlled by the ABS Pump Controller PC111 (part-no. 1270 0002). Useable PC111 units with the
XSGDWH¿UPZDUH9HU
0825-0002
Figure 1 Pump controller PC111
7KLVPDQXDOLVDVXSSOHPHQWWRWKHVWDQGDUGPDQXDOVRIWKH3&DQGVLPSOL¿HGPDQXDORIWKH$79$OO
connections must be carried out in accordance to the enclosed wiring diagram.
General Information
Main switch –Q0 interrupted the total control panel.
Fuse – F2 only protects the controller – A1. VFD –A10 remains active.
m
Analogue and digital level-inputs of PC111 are not intrinsically safe. In Ex-applications additional ap-
propriate safeguards are necessary.
Fuse – X1/8 protects circuit of accumulator (option).
Key lockable steel cabinet with separate wall brackets and cable glands.
•
•
•
•