background image

 

Installation and Operating Instructions 

7

 

ABS submersible sewage pump AFP 0831S and 0841S

 

Setup and installation

ATTENTION 

All relevant regulations covering sewage pumping installations and, where 

applicable, explosion-proof installations must be complied with.

c

  The cable duct to the control panel should be made gas-tight by filling with foam after the power 

supply and control circuit cables have been laid.

m

  Particular attention must be paid to the safety regulations covering work in closed areas in 

sewage plants as well as good general technical practices . 

.1 

Installation example in concrete sump

       Legend

1000-00

1

Sump cover 

2

Venting line 

3

Sump cover 

4

Sleeve for cable 
protective duct to
the control panel

5

Chain 

6

Inflow line 

7

Ball type float switch 

8

Submersible pump 

9

Concrete sump 

10

Pedestal 

11

Guide tube 

12

Discharge line 

13

Non-return valve 

14

Gate valve 

15    Power cable to motor

                              Installation example in concrete sump

.2 

Discharge line

The discharge line must be installed in compliance with the relevant regulations. 

DIN 1986/100 and EN 12056 applies in particular to the following:

The discharge line should be fitted with a backwash loop (180° bend) located above the backwash level and 

should then flow by gravity into the collection line or sewer.
The discharge line should not be connected to a down pipe.
No other inflows or discharge lines should be connected to this discharge line.

ATTENTION 

The discharge line should be installed so that it is not affected by frost.

-

-
-

Summary of Contents for AFP 0831S

Page 1: ...www absgroup com ABS submersible sewage pump AFP 0831S and 0841S 1007 00 15975144GB 05 2010 GB Installation and Operating Instructions ...

Page 2: ...mps in explosive zones 5 1 2 Technical data 5 1 2 1 Nameplate 5 2 Safety 6 3 Transport 6 4 Setup and installation 7 4 1 Installation example in concrete sump 7 4 3 Electrical connection 8 4 3 1 Wiring diagrams 8 4 3 2 Checking direction of rotation 9 4 3 3 Changing direction of rotation 9 5 Commissioning 10 6 Maintenance 10 6 1 General maintenance hints 10 6 2 Commentary on maintenance of lifting ...

Page 3: ...hermal sensing system connected If ball type float switches are used these must be connected to an intrinsically safe electrical circuit Protection type EX i in accordance with VDE 0165 Dismantling and repair of submersible explosion proof motors may only be carried out by approved personnel in specially approved workshops 1 2 Technical data Maximum noise level 70 dB This may be exceeded in certai...

Page 4: ...3 h Hmax Max Head m Ø Imp Impeller diameter mm DN Discharge diameter mm SS Water pressure tight IP 68 Protection type Standard version nameplate 2 Safety The general and specific Health and Safety requirements are described in detail in the Safety Instructions for ABS Products booklet If anything is not clear or you have any questions as to safety make certain to contact the manufacturer ABS 3 Tra...

Page 5: ...ne 3 Sump cover 4 Sleeve for cable protective duct to the control panel 5 Chain 6 Inflow line 7 Ball type float switch 8 Submersible pump 9 Concrete sump 10 Pedestal 11 Guide tube 12 Discharge line 13 Non return valve 14 Gate valve 15 Power cable to motor Installation example in concrete sump 4 2 Discharge line The discharge line must be installed in compliance with the relevant regulations DIN 19...

Page 6: ...on the control panel must comply with the circuit diagram of the control panel as well as the motor connection diagrams and must be carried out by a qualified person All relevant safety regulations as well as general good technical practice must be complied with ATTENTION For use in the open air the following VDE regulations apply Submersible pumps used outdoors must be fitted with a power cable o...

Page 7: ...rection of rotation is correct if the impeller propeller rotates in a clockwise manner when viewing down from the top of the placed unit 1020 00 ATTENTION The start reaction is anti clockwise Rotor rotation NOTE If a number of pumps are connected to a single control panel then each unit must be individually checked ATTENTION The mains supply to the control panel should have a clockwise rotation If...

Page 8: ...ed function easily Have the hydraulics been vented in the case of dry installed pumps 6 Maintenance c Before commencing any maintenance work the unit should be completely disconnected from the mains by a qualified person and care should be taken that it cannot be inadvertently switched back on m When carrying out any repair or maintenance work the safety regulations covering work in enclosed areas...

Page 9: ...ll Quantity AFP 50 Hz AFP 60 Hz Pump Type Litres Pump Type Litres AFP 0831 S22 4 0 6 AFP 0831 S25 4 0 6 AFP 0841 S13 4 0 6 AFP 0841 S16 4 0 6 AFP 0841 S22 4 0 6 AFP 0841 S25 4 0 6 An oil change is only necessary if a fault occurs m Repair work on explosion proof submersible pumps may only be carried out by approved personnel in approved workshops When carrying out repairs only original spare parts...

Page 10: ...12 Installation and Operating Instructions ABS submersible sewage pump AFP 0831S and 0841S ...

Page 11: ... aux normes ou à d autres documents normatifs ES Objeto de esta declaración están conformes con las siguientes normas u otros documentos normativos PT Aque se refere esta declaracáo está em conformidade com as Normas our outros documentos normativos IT Ai quali questa dichiarazione si riferisce sono conformi alla seguente norma o ad altri documenti normativi NL Waarop deze verklaring betrekking he...

Page 12: ...ABS Production Wexford Ltd Clonard Road Wexford Ireland Tel 353 53 91 63 200 Fax 353 53 91 42335 www absgroup com ...

Reviews: