Ultima OPIR-5 Detector
23
4.4.1 Setup Options Sheet
SE
- Apply Magnet when this code is showing to enter Setup.
bb
- Apply magnet when this code is showing to alter the options for Beam Block
5
to
60
- Select how many seconds before sending beam block fault
___________
0
to
60
- Select minutes of beam block before sending optical fault
___________
01
- Apply magnet when this code is showing to alter the options for Analog Output #1
SPL (Split Range) on
or
oF
f - Select whether Split Range is on or off
___________
02
- Apply magnet when this code is showing to alter the options for Analog Output #2
on
or
oF
f – Select whether 0-5000 (0-2000) ppm•m range is available
AL1
- Apply magnet when this code is showing to alter the options for Alarm Relay #1
En
or
dE
- Select whether relay is Energized or De-energized
___________
LA
or
nL
- Select whether relay is Latching or Non-latching
___________
20
00 to
45
00 (
8
00 to
18
00) - Select where relay alarm level is set
(in ppm•m)
___________
AL2
- Apply magnet when this code is showing to alter the options for Warn Relay #2
En
or
dE
- Select whether relay is Energized or De-energized
___________
LA
or
nL
- Select whether relay is Latching or Non-latching
___________
0.5
(
0.1
) to
A3
level - Select where relay alarm level is set (in LEL•m)
___________
AL3
- Apply magnet when this code is showing to alter the options for Alarm Relay #3
En
or
dE
- Select whether relay is Energized or De-energized
___________
LA
or
nL
- Select whether relay is Latching or Non-latching
___________
AL2
level to
4.5
(
0.8
) - Select where relay alarm level is set (in LEL•m)
___________
Fi
- Saves changes and exits Setup.
Fi
- Apply magnet when this code is showing to save changes and exit Setup.
NOTE:
Values in parentheses are for the Heavy Hydrocarbon (Propane) unit.