21
Warning
Hazardous voltage may be present within the
panel when connecting electronic accesso-
ries. Remove all sources of power to the ATS
panel before connecting Ekip modules.
Ekip Connect Sofware and Bluetooth and
Programming -modules are suitable for all
ZTS(D) 30-1200 A, 200-480 Vac automatic
transfer switches, refer to chapters 5.1-
5.3. in O&M Manual 1SCC303039M0201 for
more details on:
• Ekip Connect -software
• Ekip Programming -module
Ekip Signalling and Com modules are suit-
able for all ZTS(D) 30-1200 A, 200-480 Vac
automatic transfer switches. These mod-
ules are mounted with auxiliary power
supply module, OXEA1 (refer to page 36
for further details).
Ekip-modules mounted with auxiliary
power supply module are (see chapters
5.4-5.8 in O&M Manual
1SCC303039M0201).
•
Ekip Signalling 2K-_
• Ekip Com modules
• Ekip Com Modbus RTU
• Ekip Com Profibus DP
• Ekip Com DeviceNet
• Ekip Com Modbus TCP
• Ekip Com Profinet
• Ekip Com EtherNet/IP
• Ekip Link
—
Fig. 14 Ekip Signalling, Com and Link -modules
are mounted to automatic transfer switch OX_
with a auxiliary power supply module, OXEA1
—
Electronic accessories
For details on usage of electronic
accessories and Ekip connect software,
refer detailed catalog.