12
Ze nit h Z T S ( D) 3 0 -1 2 0 0A AT S , Q U I CK STA RT U S E R M A N UA L
—
Settings (Optional)
Time delays
Default Value
Possible range
Override momentary outage (separate for S1 and S2)
2 s
0-60 s
Transfer from S1 to S2 (separate for S2 to S1)
2 s
0-3600 s
Center-off delay
0 s
0-300 s
Generator stop
0 s
0-60 min
Set points
Voltage and frequency drop-out
±15% of nominal
±20% of nominal
Voltage and frequency pick-up
±14% of nominal
±19.5% of nominal
In-phase Monitor
On
Off, On
Manual Retransfer
Off
Off, On
Commit Transfer
Off
Off, On
Application
S1-Transformer/
S2-Generator
See manual
—
Table 3
Settings can be changed via the HMI as shown in Figure 5 and 6. See section 4 of the
ZTG(D) O&M for further detail. A password is required to change parameters; the default
password is 00001. Alternatively, settings can be changed with Ekip Connect 3 software
using Ekip Programming module.
—
Fig. 5