![ABB XIO-00 User Manual Download Page 28](http://html.mh-extra.com/html/abb/xio-00/xio-00_user-manual_3045261028.webp)
28
| XIO USER MANUAL | 2106424MNAB
To unpack the XIO and inspect for damaged, missing, or incorrect parts:
–
Inspect the shipping carton for damage.
–
Carefully remove items from the carton.
–
Keep all shipping materials to return parts.
–
Compare the packing list with the materials received. Check for any missing or incorrect parts.
–
Inspect each item for damage: XIO exterior and optional equipment, if purchased.
If there are missing, incorrect, damaged parts or noticeable defects, call the ABB main office number
listed on the last page of this manual.
3.4
Basic hardware installation
This is an overview of a typical hardware installation. For different installations, call the ABB main office
number listed on the last page of the manual.
NOTICE – Equipment damage
. The XIO must always be mounted on a horizonal DIN rail, never
vertically.
NOTICE – Equipment damage
. Before powering the XIO, perform all the procedures in the order
presented in this section.
DANGER – Serious damage to health / risk to life
. Use properly insulated tools and wear a
grounding strap to eliminate static electricity when connecting or disconnecting wires. Mishandling
may cause a static electric discharge resulting in bodily injury and damage to the electronic
components.
3.4.1
Ground the controller
The XIO must be mounted on a grounded DIN rail.
NOTICE – Equipment damage
. The controller must be mounted on a DIN rail bonded to an
earthing terminal. The bonding conductor must have a cross sectional area of at least 4 mm
2
(12
AWG).
To ground the DIN rail:
3.4.2
Standalone mounting
To mount the XIO:
IMPORTANT NOTE
: To remove the XIO, insert a slotted screwdriver into the access slot of the
DIN rail and release the clip to loosen. See section
Summary of Contents for XIO-00
Page 54: ...54 XIO USER MANUAL 2106424MNAB Figure 4 24 Default XIO Interface configuration ...
Page 147: ...XIO USER MANUAL 2106424MNAB 147 Figure 7 30 FileZilla New Site window ...
Page 148: ...148 XIO USER MANUAL 2106424MNAB Figure 7 31 Open the Flash AppData ssh directory ...
Page 149: ...XIO USER MANUAL 2106424MNAB 149 Figure 7 32 Upload public key from laptop to device ...
Page 150: ...150 XIO USER MANUAL 2106424MNAB Figure 7 33 Verify public key upload is complete ...