Mounting the NM Motor Operator on Left Side of VersaRupter A-mech
A left hand shaft extension is supplied if the NM motor is
ordered for left side applications. Use M8 or 5/16” bolts
and hardware to secure mounting bracket and motor.
1. Follow the instructions for installing the left hand
shaft extension. Once complete, locate the mounting
holes for the motor bracket located on the left side of
the switch and bolt the bracket to the frame as shown
in figure 47. Make sure the switch is in the open posi-
tion.
2. Rotate the splined tube on the motor to achieve a 4-8
mm spacing as shown in figure 48.
3. Adjust the spacing on the operating mechanism to
match the required spacing found in figure 44 located
in the instructions to mount the motor to an A-
mechanism.
4. Slide the motor onto the left hand shaft extension and
secure to the motor bracket with bolts, washers, lock
washers, and nuts as shown in figure 49.
4-8 mm
Figure 47
Figure 48
Figure 49
Figure 50
Summary of Contents for VersaRupter
Page 74: ...VersaRupter MV Indoor Switch Installation and Operation Manual 74 Auxiliary Switch Kit ...
Page 75: ...VersaRupter MV Indoor Switch Installation and Operation Manual 75 Chain Drive Assembly ...
Page 76: ...VersaRupter MV Indoor Switch Installation and Operation Manual 76 Left Hand Shaft Extension ...
Page 77: ...VersaRupter MV Indoor Switch Installation and Operation Manual 77 Mechanical Door Interlock ...
Page 80: ...VersaRupter MV Indoor Switch Installation and Operation Manual 80 HE HM Handles ...
Page 82: ...VersaRupter MV Indoor Switch Installation and Operation Manual 82 Notes ...