Mounting the NM Motor Operator on A-Mechanism
The NM motor operator can be installed on either the oper-
ating mechanism or a left hand shaft extension. The in-
stallation instructions are similar for either application but
instructions can be found for installation on the left side of
the VersaRupter. Further instructions can be found in the
manual for the NM motor operator supplied with the motor
concerning wiring and other data. Use M8 or 5/16” bolts
and hardware to secure mounting bracket and motor.
1. Ensure that the VersaRupter is in the open position
and the A-mechanism is not charged. Locate the
mounting holes for the motor bracket on the A-
mechanism. See figure 42.
2. Rotate the spline on the NM motor till the spacing is
within 4-8 mm as shown in figure 43.
3. Rotate the splined shaft on the A-mechanism counter
clockwise to remove the rotational variability in the
shaft as shown in figure 44. This can be done by hand
and does not require an operating handle.
4-8 mm
Figure 42
Figure 43
Figure 44
Summary of Contents for VersaRupter
Page 74: ...VersaRupter MV Indoor Switch Installation and Operation Manual 74 Auxiliary Switch Kit ...
Page 75: ...VersaRupter MV Indoor Switch Installation and Operation Manual 75 Chain Drive Assembly ...
Page 76: ...VersaRupter MV Indoor Switch Installation and Operation Manual 76 Left Hand Shaft Extension ...
Page 77: ...VersaRupter MV Indoor Switch Installation and Operation Manual 77 Mechanical Door Interlock ...
Page 80: ...VersaRupter MV Indoor Switch Installation and Operation Manual 80 HE HM Handles ...
Page 82: ...VersaRupter MV Indoor Switch Installation and Operation Manual 82 Notes ...