VersaRupter MV Indoor Switch | Installation and Operation Manual
12
Mounting the Open Fuse Auxiliary Switch
The open fuse auxiliary switch can only be installed on the A-
mechanism and a fuse base equipped with fuse tripping. This
switch has two contacts, one normally open and one normally
closed. It is actuated by the fuse tripping tie rod linkage con-
nected to the type CEF fuse base.
1. Locate the mounting hole and slot on the side of the A-
mechanism with the operating shaft shown in figure 11.
2. Bolt the open fuse auxiliary switch to the mounting hole on
the A-mechanism and loosely install the screw hardware to
allow the switch to rotate into the slot, pictured in figure
12.
3. Place the white disk onto the half-moon shaft and rotate
the switch into place as shown in figure 13.
4. Rotate the white disk with your finger and mark the hole
directly adjacent to the white roller on the switch as
shown in figure 14.
Figure 11
Figure 12
Figure 13
Figure 14
Summary of Contents for VersaRupter
Page 74: ...VersaRupter MV Indoor Switch Installation and Operation Manual 74 Auxiliary Switch Kit ...
Page 75: ...VersaRupter MV Indoor Switch Installation and Operation Manual 75 Chain Drive Assembly ...
Page 76: ...VersaRupter MV Indoor Switch Installation and Operation Manual 76 Left Hand Shaft Extension ...
Page 77: ...VersaRupter MV Indoor Switch Installation and Operation Manual 77 Mechanical Door Interlock ...
Page 80: ...VersaRupter MV Indoor Switch Installation and Operation Manual 80 HE HM Handles ...
Page 82: ...VersaRupter MV Indoor Switch Installation and Operation Manual 82 Notes ...