![ABB UNO-2.0-I-OUTD Product Manual Download Page 69](http://html.mh-extra.com/html/abb/uno-2-0-i-outd/uno-2-0-i-outd_product-manual_4189069.webp)
- 69 -
000068DG
7 - Operation
EXXX
Lun 22 Lug 15:55
Inverter OK
Lun 22 Lug 15:55
Type OUTD
P/N -3xxx-
S/N XXXXXX
FW rel. XXXX
E-day 0.0kWh
$-day 0.0EUR
E-tot 0kWh
E-par 0kwh
Pout 330W
COSp 1.000
>No regolazione
Tamb 29.5`C
Tboost 26.6`C
DOWN
UP
DOWN
UP
DOWN
UP
DOWN
UP
DOWN
UP
DOWN
UP
Ppk 0W
PpkDay 0W
DOWN
UP
DOWN
UP
Vgrid 230V
Vgrid Av 230V
Igrid 0.0A
Fgrid 50.0Hz
Vin 0V
Iin 0.0A
DOWN
UP
DOWN
UP
DOWN
UP
Pin 0W
Riso 20.0Mo
Vgnd 0.0V
DOWN
UP
DOWN
UP
Vbulk 0V
Vbulk_m 0V
DOWN
UP
DOWN
UP
Inverter status.
The code for any malfunction will be displayed.
Date and time
as set on the inverter
Errors/Warnings
On
No
Errors/Warnings
Type:
Outdoor inverter type (OUTD)
P/N:
ABB product identification code
S/N:
Sequential serial number
FW rel. :
Firmware version installed
E-day:
Energy produced today
$-day :
Today's savings/earnings
E-tot:
Energy produced since the inverter was commissioned
E-par :
Partial energy produced
Pout:
Instantaneous output power
Phase difference
set for feeding in reactive power
Reactive power regulation mode
currently set
Tamb:
Internal temperature in the inverter circuit (DC/AC)
Tboost:
Internal temperature in the booster circuit (DC/DC)
Ppk:
Maximum output power peak since the inverter was commissioned
PpkDay:
Maximum daily output power peak
Vgrid:
Output voltage
Vgrid Av:
Average R-phase output voltage
Igrid:
Output current
Fgrid:
Output frequency
Vin:
Input voltage
Iin:
Input current
Pin:
Instantaneous input power
Riso:
Insulation resistance on DC input side (PV generator)
Vbulk:
Internal voltage at the bulk capacitor terminals (booster circuit)
Vbulk_m:
Internal voltage at the bulk capacitor mid-point (booster
circuit)