Figure 23. Dimensions and angles
Figure 24. Lifting
CAUTION
Four lifting ropes of sufficient length must be used
when lifting several units or a whole switchgear (4
units at the most, or a maximum length of 2 m).
Lifting by crane
Operations after lifting
a) Dismantle the lifting hooks.
b) The same hooks are used again for the next unit.
2.4 Temporary storage
2.4.1 General warnings and cautions
CAUTION
The packing must be kept indoors immediately
after arrival. The conditions must meet the
environmental requirements of the IEC 60721-3-1
Standard, classification 1K3
CAUTION
The vapour corrosion inhibitors placed in the units
for protection against humidity during temporary
storage and transport must not be removed until
installation is completed
CAUTION
The duration of the protective effect of the packing
is limited to a few months when stored indoors in a
dry place. ABB should be consulted in the case of
longer storage periods or if the storage conditions
differ from those indicated
2.4.2 Optimum storage conditions
Definition: Optimum temporary storage, without
negative consequences, depends on compliance
with the minimum requirements for the units and
packing materials.
Minimum air temperature
°C
-5
(*)
Maximum air temperature
°C
+40
Minimum relative humidity
%
5
Maximum relative humidity
%
95
Rate of temperature change
°C/min
0,5
(*) For service temperature -25 °C and storage temperature -40 °C,
please ask ABB
Table 3. Climatic conditions according to IEC 60721-3-1,
classification 1K3