D I S T R I B U T I O N S O LU T I O N S
21
—
Medium voltage cable lengths and locations
Details
190 mm width
375 mm width
500 mm width
600 mm width
750 mm width
A (mm)
B (mm)
A (mm)
B (mm)
A (mm)
B (mm)
A (mm)
B (mm)
A (mm)
B (mm)
SDC
Basic
–
–
920
210
920
275
–
–
–
–
With CT
–
–
–
–
530
275
–
–
530
265
SDM
Basic
–
–
–
–
–
–
–
–
525
(1)
275
(1)
SDD
Basic
–
–
–
–
–
–
–
–
920
210
SFC
292 mm fuse
–
–
600
200
600
240
–
–
570
400
442 mm fuse
–
–
450
200
450
240
–
–
570
400
SBC/
SBC-W
Basic
–
–
–
–
–
–
–
–
610
355
With CT
–
–
–
–
–
–
–
–
500
340
DRC
Basic
–
–
870
180
670
240
–
–
–
–
With CT
–
–
–
–
530
275
–
–
–
–
SBR
Basic
–
–
–
–
–
–
–
–
400
390
UMP
With CT
–
–
–
–
–
–
–
–
550
270
HBC
Basic
–
–
–
–
608
275
–
–
–
–
With CT
–
–
–
–
460
325
–
–
–
–
With sensor
Kevcr
–
–
–
–
583/450
(3)
275
–
–
–
–
RLC/RRC H1700 Basic
1520
265
–
–
–
–
–
–
–
–
With SBR
1495
310
–
–
–
–
–
–
–
–
With HBC
1435
280
–
–
–
–
–
–
–
–
RLC/RRC H2000 Basic
1645
305
–
–
–
–
–
–
–
–
WBC/BME
Baseplate or
with CT
–
–
–
–
–
–
600
150
(2)
600
165
(2)
(1) With optional cable terminal
(2) Distance between side wall of panel and first connection cable
(3) Central phase (L2)
RLC unit
3.3.3 Medium voltage cable locations and lengths
The medium voltage cable lengths (distance of the
cable connection point from the floor) depend on
the units and accessories used.
The following figures and table show the cable
lengths and locations for the different units.