Rectifier
Defeat plate
6. Disengage the two leads of the coil from the (+) & (-)
terminals of the rectifier (when fitting the
replacement coil engage the two leads with the
terminals of the rectifier).
4. Undo the M3 nylock nut (when
re-assembling tighten the nylock nut till
the end is flush with the end of the screw).
5. Undo the two M3 x10 socket head cap screws to
remove the defeat plate (when fitting these two
screws on the replacement blocking coil, add a drop of
loctite before engaging four threads).
3. Undo the four M3 pan head screws with spring
washers to remove the blocking magnet with coil
(when replacing the blocking magnet with coil,
tighten each screw to 0.6 Nm).
50
U N I G E A R Z V C
M E D I U M V O L T A G E P R O D U C T S
—
9/6 ZVC racking
blocking coil
replacement 2 of 2
—
9/6