Specifications
42 TZIDC-200,
TZIDC-210, TZIDC-220
42/18-85-EN
9.1.10 Accessories
Mounting material
Attachment kit for linear actuators to DIN / IEC 534 / NAMUR
Attachment kit for part-turn actuators to VDI / VDE 3845
Attachment kit for integral mounting to control valves
Attachment kit for actuator-specific attachment upon request
Ex d cable entry
Cable gland and pipe plug approved for Ex d, securing adhesive
Pressure gauge block
With pressure gauges for supply and output pressure. Pressure
gauges with housing ø 28 mm (1.10 inch), with connection block in
aluminum, black with installation material for mounting on positioner
Filter regulator
All metal version in brass, varnished black, bronze filter element,
40 µm, with condensate drain.
Max. pre-pressure 16 bar (232 psi), output adjustable to 1.4 ... 6 bar
(20.31 ... 87.02 psi)
PC adapter for communication
LKS adapter f. plug conn. to positioner
FSK modem for HART communication
(see data sheet 63_6.71)
PC software for remote configuration and operation
DSV401 (SMART VISION) with DTM for TZIDC / TZIDC-200
available on CD ROM (see data sheet 63_1.20)
9.2 TZIDC-210
9.2.1 Communication
Profiles
Profibus PA profile for process
devices
Electro-pneumatic actuators V3.0
Block types
1 AO Functional block
1 Transducer block
1 physical block
Physical Layer
In compliance with IEC 61158-2
Transmission rate
31.25 Kbit/s
Supply voltage
Power feed from the PA bus,
9.0 ... 32.0 V DC
Max. permissible voltage
35 V DC
Power consumption
10.5 mA
Current in the event of an
error
15 mA (10.5 mA + 4.5 mA)
9.2.2 Description
Device name
TZIDC-X10
PNO ID no.
0x0639
Dev. ID
0X3200028xyz
Bus address
Between 0 and 126, default address
126
9.2.3 Output
Range
0 ... 6 bar (0 ... 90 psi)
Air capacity
at 1.4 bar (20 psi) supply pressure
5.0 kg/h = 3.9 Nm
3
/h = 2.3 scfm
at supply pressure of 6 bar (90 psi)
13 kg/h = 10 Nm
3
/h = 6.0 scfm
Output function
For single or double-acting actuators,
air is vented from actuator or actuator
is blocked in case of (electrical) power
failure
Shut-off values
end position 0 % = 0 ... 45 %
end position 100 % = 55 ... 100 %
9.2.4 Travel
Ste
Rotation angle
Used range
25 … 120°
rotary actuators, optionally 270°
25 … 60°
linear actuators
Travel time
prolongation
Setting range
0 ... 200 seconds, separately for each
direction
9.2.5 Air
supply
Instrument air
free of oil, water and dust acc. to
DIN / ISO 8573-1
pollution and oil content according to
Class 3 (purity: max. particle size:
5
µ
m, max. particle density:
5 mg / m
3
; oil content: max.
concentration: 1 mg / m
3
; pressure
dew point: 10 K below operating
temperature
Supply pressure
1.4 ... 6 bar (20 ... 90 psi)
IMPORTANT (NOTE)
Do not exceed the maximum operating pressure of the
actuator!
Air consumption
< 0.1 kg/h / 0.05 scfm (independent
of supply pressure)