Commissioning
28 TZIDC-200,
TZIDC-210, TZIDC-220
42/18-85-EN
7 Commissioning
7.1 TZIDC-200
bieten
1.
Feed in pneumatic auxiliary power.
2.
Feed in electrical supply power.
• Feed in setpoint current 4 ... 20 mA (ter11 / -12)
3.
Check mount:
• Press and hold
, and press or until operating mode 1.3 (manual adjustment
within the sensor range) is displayed. Release
.
• Press or to move the actuator into the mechanical end position; check the end
positions; rotation angle is displayed in degrees; for high-speed mode, press and
simultaneously.
Recommended range:
- between -28 ... 28° for linear actuators
- between -57 ... 57° for part-turn actuators
Minimum angle: 25°
4.
Run Autoadjust.
For linear actuators
1)
:
• Press and hold
until
is displayed; release the control button.
• Press
again and hold down until the countdown ends.
• Release
; this starts Autoadjust.
For part-turn actuators
1)
:
•
Press and hold
until
is displayed; release the control button.
•
Press
again and hold it down until the countdown ends.
•
Release
; this starts Autoadjust.
If Autoadjust is successful, the parameters will be stored automatically and the positioner will
revert to operating mode 1.1.
If an error occurs during Autoadjust, the process will be terminated with an error message. If
this happens, press and hold down or for approximately three seconds. The unit will switch
to the operating level, mode 1.3 (manual adjustment within the sensor range). The mount is
checked and corrected if necessary. Autoadjust then runs again.
IMPORTANT (NOTE)
Autoadjust does not always result in optimum control conditions.
1) The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for
linear actuators and clockwise (CLOCKW) for part-turn actuators).