Ex relevant specifications
58 TZIDC-200,
TZIDC-210, TZIDC-220
42/18-85-EN
10.2.3 IECEx
10.2.3.1 Flameproof enclosure
Designation:
Ex d IIC T4/T5/T6
Type Examination Test
Certificate:
IECEx BVS 07.0030X, Issue No.: 0
Type:
TZIDC-210
Temperature class:
T4, T5, T6
Permissible ambient
temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C
Standards:
IEC 60079-0: 2011
IEC 60079-1: 2007
Electrical data
Voltage:
≤
30 V AC/DC
Amperage:
≤
20 mA
Pneumatic data
Supply pressure:
≤
6 bar
Thermal data
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C
Change from one to two columns
Special conditions for IECEx, flameproof enclosures
• The positioner is designed for a maximum acceptable ambient temperature range
between -40 … 85 °C.
• If the positioner is used at an ambient temperature above 60 °C or below -20 °C, use cable
entries and lines approved for a service temperature corresponding to the maximum ambient
temperature increased by 10 K or corresponding to the minimum ambient temperature,
respectively.
• Variants that also meet the requirements for the "intrinsically safe" type of ignition protection
may not be used as "intrinsically safe", if they have been previously used as a flameproof
type of ignition protection.
Change from one to two columns