background image

 

Safety

 

42/18-85-EN TZIDC-200, 

TZIDC-210, TZIDC-220 

 

1 Safety 

 

 

1.1 

General information and notes for the reader 

 

 

You must read these instructions carefully prior to installing and commissioning the device. 
These instructions are an important part of the product and must be kept for future reference. 
These instructions are intended as an overview and do not contain detailed information on all 
designs for this product or every possible aspect of installation, operation and maintenance. 
For additional information or if specific problems occur that are not discussed in these 
instructions, contact the manufacturer. 
The content of these instructions is neither part of any previous or existing agreement, promise 
or legal relationship nor is it intended to change the same. 
This product is built based on state-of-the-art technology and is operationally safe. It has been 
tested and left the factory in perfect working order from a safety perspective. The information in 
the manual must be observed and followed in order to maintain this state throughout the period 
of operation. 
Modifications and repairs to the product may only be performed if expressly permitted by these 
instructions. 
Only by observing all of the safety instructions and all safety/warning symbols in these 
instructions can optimum protection of both personnel and the environment, as well as safe and 
fault-free operation of the device, be ensured. 
Information and symbols directly on the product must be observed. They may not be removed 
and must be fully legible at all times. 
 

 

1.2 Intended 

use 

 

 

 

TZIDC-200, TZIDC-210, TZIDC-220 positioners are electro-pneumatic positioning devices for 
use with pneumatically controlled actuators. 
The device may only be used for the applications listed in these operating instructions and in 
the data sheet. 
•  The maximum operating temperature must not be exceeded. 
•  The permissible operating temperature must not be exceeded. 
•  The housing protection type must be observed during operation. 
 

 

1.3 

Target groups and qualifications 

 

 

Installation, commissioning, and maintenance of the product may only be performed by trained 
specialist personnel who have been authorized by the plant operator to do so. The specialist 
personnel must have read and understood the manual and comply with its instructions. 
Prior to using corrosive and abrasive materials for measurement purposes, the operator must 
check the level of resistance of all parts coming into contact with the materials to be measured. 
ABB Automation Products GmbH will gladly support you in selecting the materials, but cannot 
accept any liability in doing so. 
The operators must strictly observe the applicable national regulations with regards to 
installation, function tests, repairs, and maintenance of electrical products. 
 

 

Summary of Contents for TZIDC-200

Page 1: ...Operating Instruction 42 18 85 EN Electro Pneumatic Positioner TZIDC 200 TZIDC 210 TZIDC 220 for 4 20 mA two wire technology HART PROFIBUS PA FOUNDATION fieldbus ...

Page 2: ...straße 72 32425 Minden Germany Tel 49 571 830 0 Fax 49 571 830 1806 Customer service center Phone 49 180 5 222 580 automation service de abb com Copyright 2016 by ABB Automation Products GmbH Subject to changes without notice This document is protected by copyright It assists the user in safe and efficient operation of the device The contents of this document whether whole or in part may not be co...

Page 3: ...safety instructions 10 3 Design and function 12 4 Mounting 13 4 1 Operating conditions at installation site 13 4 2 Mechanical mount 13 4 2 1 General information 13 4 2 2 Mounting on linear actuators 15 4 2 3 Mounting on part turn actuator 20 5 Electrical connections 23 5 1 Screw terminal assignments 24 5 2 Cable entry 25 5 3 Setting the mechanical feedback 25 5 3 1 Mechanical position indicator 25...

Page 4: ...3 9 2 8 Housing 43 9 2 9 Options 44 9 2 10 Accessories 44 9 3 TZIDC 220 45 9 3 1 Communication 45 9 3 2 Device name 45 9 3 3 Output 45 9 3 4 Travel 45 9 3 5 Air supply 45 9 3 6 Transmission data and influences 46 9 3 7 Environmental capabilities 46 9 3 8 Housing 46 9 3 9 Options 47 9 3 10 Accessories 47 10 Ex relevant specifications 48 10 1 TZIDC 200 48 10 1 1 FM CSA 48 10 1 2 ATEX GOST Russia GOS...

Page 5: ...ions can optimum protection of both personnel and the environment as well as safe and fault free operation of the device be ensured Information and symbols directly on the product must be observed They may not be removed and must be fully legible at all times 1 2 Intended use TZIDC 200 TZIDC 210 TZIDC 220 positioners are electro pneumatic positioning devices for use with pneumatically controlled a...

Page 6: ...ere injury WARNING Bodily injury This symbol in conjunction with the signal word Warning indicates a possibly dangerous situation Failure to observe this safety information may result in death or severe injury WARNING Bodily injury This symbol in conjunction with the signal word Warning indicates a potential electrical hazard Failure to observe this safety information may result in death or severe...

Page 7: ...e unit must be stored in dry and dust free conditions The unit is also protected by a dessicant in the packaging The storage temperature should be between 40 85 C 40 185 F The storage time is basically indefinite However the warranty conditions stipulated in the order confirmation of the supplier are valid M00406 Type V18345 Softw Rev Serial no Seriennr NL No Year Baujahr Supplypress 20 90 psi Zul...

Page 8: ...rved otherwise the type of electrical protection may be adversely affected Safe isolation of electrical circuits which are dangerous if touched is only guaranteed if the connected devices satisfy the requirements of DIN EN 61140 VDE 0140 Part 1 basic requirements for safe isolation To ensure safe isolation install supply lines so that they are separate from electrical circuits which are dangerous ...

Page 9: ...c Please Please contact Customer Center Service acc to page 2 for nearest service location 1 12 Integrated management system ABB Automation Products GmbH operates an integrated management system consisting of Quality management system to ISO 9001 2008 Environmental management system to ISO 14001 2004 Occupational health and safety management system to BS OHSAS 18001 2007 and Data and information p...

Page 10: ...ulated collection and disposal or reuse in the event of disposal or at the end of their service life ElektroG also prohibits the marketing of electrical and electronic equipment that contains certain amounts of lead cadmium mercury hexavalent chromium polybrominated biphenyls PBB and polybrominated diphenyl ethers PBDE also known as hazardous substances with restricted uses The products provided b...

Page 11: ...f use following a review Variants that also meet the requirements for the intrinsically safe type of ignition protection may not be used as intrinsically safe if they have been previously used as a flameproof type of ignition protection Secure the cable and line entries against twisting and becoming loose by applying adhesive of medium strength In the event of high torsional forces the bearing sle...

Page 12: ...ical position indicator 13 Installation kit for digital feedback with proximity switches 14 Installation kit for digital feedback with 24 V microswitches 1 TZIDC 200 only IMPORTANT NOTE With optional upgrades either the Installation kit for digital feedback with proximity switches 13 or the Installation kit for digital feedback with microswitches 24 V 14 can be used In both cases the mechanical po...

Page 13: ...be reset to factory settings Never start Autoadjust before restoring factory settings 4 1 Operating conditions at installation site IMPORTANT NOTE Before installation check whether the TZIDC 200 TZIDC 210 TZIDC 220 positioner meets the control and safety requirements for the installation location actuator or valve See chapter Specifications page 39 4 2 Mechanical mount cke 4 2 1 General informatio...

Page 14: ... range for part turn actuators 3 Restricted operating range 4 Operating range IMPORTANT NOTE During installation make sure that the actuator travel or rotation angle for position feedback is implemented correctly The maximum rotation angle for position feedback is 60 when installed on linear actuators and 120 on part turn actuators The minimum angle is always 25 ...

Page 15: ...ing table Fig 5 Mounting kit for linear actuators Lever 4 with follower pin for stroke adjustment 10 35 mm 0 39 1 38 inch or 20 100 mm 0 79 3 94 inch Follower guide 13 with two screws 10 spring washers 11 and clamp plates 12 Mount bracket 3 with two screws 6 and two shims 5 Screw 1 and shim 2 for mounting on cast iron yoke Two U bolts 7 each with two shims 8 and two nuts 9 for mounting on columnar...

Page 16: ... lever unless preassembled Fig 7 Insert spring 8 on bolt with follower pin 9 Slip the plastic washer 7 onto the bolt and compress the spring with it Insert the bolt with compressed spring into the oblong hole in the lever 6 and fasten it in the desired position using the plain washer 5 and nut 4 at the lever The scale on the lever indicates the link point for the stroke range Place the washer 2 on...

Page 17: ...d tighten the screw 7 on the lever Hold the prepared positioner with loose mount bracket 1 to the actuator so that the follower pin for the lever enters the follower guide to determine which holes on the positioner must be used for the mount bracket Attach the mount bracket 1 with screws 2 and shims 3 to the proper holes on the positioner housing Tighten the screws as evenly as possible to ensure ...

Page 18: ... Fig 10 Hold the mount bracket 3 in the proper position on the columnar yoke 3 Insert the U bolts 2 from the inside of the columnar yoke 3 through the holes for the mount bracket Add the washers 5 and nuts 6 Hand tighten the nuts IMPORTANT NOTE Adjust the height of the positioner on the cast iron yoke or columnar yoke until the lever is horizontal based on visual check at half stroke of the valve ...

Page 19: ...e working range for the position sensor Moving the link point inwards increases the rotation angle of the sensor Moving the link point outwards reduces the rotation angle of the sensor Adjust the actuator stroke so that you can make use of as large an angle of rotation as possible symmetrical around the center position on the position sensor Recommended range for linear actuators between 28 28 Min...

Page 20: ...I VDE 3845 the following mounting kit is available Fig 12 Adapter 1 with spring 5 Four screws M6 4 four spring washers 3 and four shims 2 for attaching the mounting bracket 6 to the positioner Four screws M5 7 four spring washers 8 and four shims 9 for attaching the mounting bracket to the actuator Required tools Wrench size 10 13 Allen key size 3 ...

Page 21: ...ome position and rotational direction of the actuator determine in which position the feedback shaft 1 for the positioner must be pre adjusted and in which position the adapter 2 must be placed to enable the positioner to travel within the proper range the arrow on the rear of the device must travel within the admissible range see Fig 3 Pre adjust feedback shaft Place the adapter in the proper pos...

Page 22: ...18 85 EN 2 Screwing mounting bracket on to positioner Fig 14 1 Mounting bracket 3 Screwing positioner on to actuator Fig 15 IMPORTANT NOTE After mounting check whether the working range for the actuator matches the sensor range for the positioner ...

Page 23: ...module and the proximity switches or microswitches insert the wire ends from the left into the respective screw terminals and hand tighten the screws access from above To connect a plug in module insert the wire ends from above in the appropriate screw terminals and hand tighten the screws access from the side Fig 16 Electrical connection A Basic model B Options 1 Analog input Bus connector 2 Digi...

Page 24: ...le for digital feedback 1 or service switch of emergency shutdown module 3 Module for digital position feedback 1 or terminals of the shutdown module 4 Installation kit for digital position feedback either proximity switches or 24 V microswitches 5 Same as 4 6 Digital output DO 1 7 Digital input DI 1 8 Signal 4 20 mA 9 Grounding screw 1 TZIDC 200 only ...

Page 25: ... pipe thread 1 4 18 NPT Cable thread M20 x 1 5 air pipe thread G 1 4 Cable thread G 1 2 air pipe thread Rc 1 4 As an option one thread can be fitted with a cable gland and the other with a pipe plug if necessary Fig 18 Cable entry 1 Pipe plug 2 Cable gland 5 3 Setting the mechanical feedback 5 3 1 Mechanical position indicator 1 Loosen the screws for the housing cover and remove it 2 Rotate the po...

Page 26: ...ating to the right of the feedback shaft viewed from the front Move the valve by hand into the upper switching position Use a screwdriver to adjust the slot sensor for proximity switch 2 upper contact until it closes the contact i e until shortly before entering the proximity switch on the feedback shaft the slot sensor enters proximity switch 2 when rotating to the left of the feedback shaft view...

Page 27: ...ositioners or actuators Provisions should be made to ensure that in the event of an error the pressure does not rise above 6 bar 90 psi Fig 19 Pneumatic connections 1 Pneumatic outputs 2 Supply air 3 Filter screw All pneumatic piping connections are located on the right side of the positioner To connect the pneumatic pipes G1 4 or 1 4 18 NPT tap holes are provided The positioner is labeled accordi...

Page 28: ... hold down until the countdown ends Release this starts Autoadjust For part turn actuators 1 Press and hold until is displayed release the control button Press again and hold it down until the countdown ends Release this starts Autoadjust If Autoadjust is successful the parameters will be stored automatically and the positioner will revert to operating mode 1 1 If an error occurs during Autoadjust...

Page 29: ...1 with adaptation the control parameter 1 1 Control mode1 without adaptation the control parameter 1 2 Manual adjustment 2 in the operating range Adjust with or 3 1 3 Manual adjustment 2 in the sensor range Adjust with or 3 1 Since self optimization in operating mode 1 0 is subject to several factors during control operation with adaptation incorrect adjustments could be made over an extended peri...

Page 30: ... 1 1 in the operating level 1 Switch to the configuration level Press and hold and simultaneously Press briefly Wait until the countdown goes from 3 to 0 Release and is displayed 2 Switch to parameter group 3 _ Press and hold and simultaneously Press twice briefly is displayed Release and is displayed 3 Select parameter 3 2 Press and hold Press twice briefly is displayed Release 4 Change parameter...

Page 31: ...ess and hold Press twice briefly is displayed Release Press briefly to select Press and hold till the countdown goes from 3 to 0 The new parameter setting is saved and the positioner automatically returns to the working level and continues to run in the operating level that was active before calling up the configuration level conf mA C ...

Page 32: ...sition check the end positions rotation angle is displayed in degrees for high speed mode press and simultaneously Recommended range between 28 28 for linear actuators between 57 57 for rotary actuators Minimum angle 25 4 Go back to the bus level Press and hold down and once the countdown has gone from 3 to 0 release and is displayed 5 Run Autoadjust Check that the unit is on the bus level REMOTE ...

Page 33: ...pproximately three seconds The unit will switch to the operating level mode 1 3 manual adjustment within the sensor range The mount is checked and corrected if necessary Autoadjust then runs again 6 Set potential dead band and tolerance band This step is only required for critical e g very small actuators It is not necessary under normal circumstances 1 The zero position is determined automaticall...

Page 34: ...ress Press or to set the correct value Press and hold down Wait for the countdown to go from 3 to 0 Release The new bus address is saved 4 Switch to parameter 1 6 Return to operating level and save the new setting Press and hold down Press and release twice is displayed Release Press and release to select Press and hold down for the countdown to go from 3 to 0 The new parameter setting is saved an...

Page 35: ...TER Displays the software revision 7 2 3 Operating modes Selection from the operating level Press and hold down Press and release as often as required to display the selected operating mode Release The position is displayed in or as a rotation angle Operating mode Mode indicator Position indicator 1 1 Positioning with fixed setpoint Use or to adjust the setpoint 1 2 Manual adjustment 1 in the oper...

Page 36: ...rating level 1 Switch to the configuration level Press and hold down and simultaneously Press and release Wait for the countdown to go from 3 to 0 Release and is displayed 2 Switch to parameter group 3 _ Press and hold down and simultaneously Press and release twice is displayed Release and is displayed 3 Select parameter 3 2 Press and hold down Press and release twice is displayed Release 4 Chang...

Page 37: ...uing to run on the operating level that was active prior to the configuration level being called up 8 Maintenance IMPORTANT NOTE In case of manipulation by users the warranty for the device is no longer valid Note that the supplied instrument air must be free of oil water and dust according to DIN ISO 8573 1 to ensure trouble free operation Essentially no maintenance is required for the positioner...

Page 38: ...must be performed at least every two years Procedure Fig 20 Slide switch for emergency shutdown module 1 Open the housing cover 2 Move the slide switch 1 from center position On to the upper and lower switch positions Off1 or Off2 and check whether the actuator is depressurized 3 Reset the slide switch to the center position On after the functional check 4 Replace the housing cover ...

Page 39: ...tal output control circuit to DIN 19234 NAMUR Supply voltage 5 11 V DC Current 0 35 mA 1 2 mA Switching state logical 0 Current 2 1 mA Switching state logical 1 Effective direction configurable normally logical 0 or logical 1 9 1 3 Travel Rotation angle Used range 25 120 rotary actuators optional 270 25 60 linear actuators Travel limit Min and max limits freely configurable between 0 100 of total ...

Page 40: ...age 75 annual average non condensing 9 1 7 Housing Material Degree of protection Aluminum protection class IP 65 optional IP 66 NEMA 4X Surface Color Electrostatic dipping varnish with epoxy resin stove hardened Case varnished black RAL 9005 matte housing cover Pantone 420 Electrical connections Screw terminals Max 1 0 mm2 AWG 17 for options Max 2 5 mm2 AWG 14 for 4 20 mA input signal IMPORTANT NO...

Page 41: ...t 2 is additionally pressurized IMPORTANT NOTE The emergency shutdown module can only be used with pneumatics with the safe position fail safe The emergency shutdown module works independently of the mother board i e all information from the final control element is available in the supervisory process control system at any time 1 The module for analog position feedback and the module for digital ...

Page 42: ... 1 Transducer block 1 physical block Physical Layer In compliance with IEC 61158 2 Transmission rate 31 25 Kbit s Supply voltage Power feed from the PA bus 9 0 32 0 V DC Max permissible voltage 35 V DC Power consumption 10 5 mA Current in the event of an error 15 mA 10 5 mA 4 5 mA 9 2 2 Description Device name TZIDC X10 PNO ID no 0x0639 Dev ID 0X3200028xyz Bus address Between 0 and 126 default add...

Page 43: ...nd transport 40 85 C 40 185 F When using proximity switches SJ2 S1N NO 25 85 C 13 185 F Relative humidity Operational with closed housing and air supply switched on 95 annual average condensation permissible Transport and storage 75 annual average non condensing 9 2 8 Housing Material Degree of protection Aluminum protection class IP 65 optional IP 66 NEMA 4X Surface Color Electrostatic dipping va...

Page 44: ...l state Position Proximity switch Lim 1 Lim 1 Lim 2 Lim 2 SJ2 SN NC 0 1 1 0 SJ2 S1N NO 1 0 0 1 IMPORTANT NOTE When using SJ2_S1N NO the TZIDC positioner may only be used at an ambient temperature range from 25 85 C Digital position feedback with 24 V microswitches1 Two microswitches for independent position signaling Switching points adjustable between 0 100 Voltage max 24 V AC DC Load rating max ...

Page 45: ...st the operating range and control parameters an automatic configuration must be run on the unit Otherwise the transducer block remains in out of service mode Diagnostic functions Self diagnostics for the positioner hardware and software valve diagnostics with enhanced alarm handling 9 3 2 Device name Device name ABB TZID C220XXXXXXXXXX Dev ID 0X3200028 TZID C220XXXXXXXXXXX 9 3 3 Output Range 0 6 ...

Page 46: ...perature For operation storage and transport 40 85 C 40 185 F When using proximity switches SJ2 S1N NO 25 85 C 13 185 F Relative humidity Operational with closed housing and air supply switched on 95 annual average condensation permissible Transport and storage 75 annual average non condensing 9 3 8 Housing Material Degree of protection Aluminum protection class IP 65 optional IP 66 NEMA 4X Surfac...

Page 47: ...tching state logical 1 function dependent on software and electronics for actuator Direction of action logical state Position Proximity switch Lim 1 Lim 1 Lim 2 Lim 2 SJ2 SN NC 0 1 1 0 SJ2 S1N NO 1 0 0 1 Digital position feedback with 24 V microswitches Two microswitches for independent position signaling Switching points adjustable between 0 100 Voltage max 24 V AC DC Load rating max 2 A Contact ...

Page 48: ...L II III Div 1 Grp E F G CSA Certification 1393920 Explosion Proof enclosure 4X T5 max 85 C CL I Div 1 Grp C D CL II Div 1 Grp E F G CL III Intrinsic Safety enclosure 4X T5 max 82 C CL I Div 1 Grp A B C D CL II Div 1 Grp E F G CL III 10 1 2 ATEX GOST Russia GOST Ukraine 10 1 2 1 Flameproof enclosure Designation II 2 G Ex d IIC T4 T5 T6 Type Examination Test Certificate DMT 02 ATEX E 029 X Type TZI...

Page 49: ...ecialist The splash guard cap must be screwed in place to achieve the IP 65 NEMA 4x protection class Operating the devices without the splash guard cap is prohibited The device may only be supplied with instrument air that is free of oil water and dust Do not use flammable gases oxygen or oxygen enriched gas Secure the cable and line entries against twisting and becoming loose by applying adhesive...

Page 50: ...values Ui 30 V Ii 320 mA Pi 1 1 W Ci 4 2 nF Li negligibly small Switch output Terminal 83 84 Maximum values Ui 30 V Ii 320 mA Pi 500 mW Ci 4 2 nF Li negligibly small Mechanical digital feedback 2 Terminals Limit1 51 52 or Limit2 41 42 For max values see EC type examination test certificate number PTB 00 ATEX 2049 X Proximity switches manuf by Pepperl Fuchs Plug in module for digital position feedb...

Page 51: ...n the name plate in a permanent manner Specific ambient conditions such as chemical corrosion should be taken into account when affixing the permanent mark Only the manufacturer may change the selected type of use following a review Variants with special certification confirming that they meet the requirements for the flameproof enclosure type of ignition protection may not be used as intrinsicall...

Page 52: ...umns Special conditions for IECEx flameproof enclosures The positioner is designed for a maximum acceptable ambient temperature range between 40 85 C If the positioner is used at an ambient temperature above 60 C or below 20 C use cable entries and lines approved for a service temperature corresponding to the maximum ambient temperature increased by 10 K or corresponding to the minimum ambient tem...

Page 53: ...6 6 nF Li negligibly small Contact input Terminal 81 82 Maximum values Ui 30 V li 320 mA Pi 1 1 W Ci 4 2 nF Li negligibly small Switch output Terminal 83 84 Maximum values Ui 30 V Ii 320 mA Pi 500 mW Ci 4 2 nF Li negligibly small Local communication interface LKS Only for connection to a programmer outside the potentially explosive area See special conditions The following modules may be operated ...

Page 54: ...y explosive atmospheres zone 2 and the prevailing conditions at the installation site It is only permissible to connect disconnect and switch live circuits when carrying out installation maintenance or repair tasks Note It is considered to be unlikely that a potentially explosive atmosphere would be present at the same time that installation maintenance or repair work was being carried out For the...

Page 55: ...ack 0 1 or 2 e Design varnish coding 1 or 2 f Device identification label 0 1 or 2 TZIDC 210 Positioner Model V18349 a012b3cd3ef XP I 2 CD T6 T5 T4 TA 82 C DIP II III 2 FG T6 T5 T4 Ta 82 C Enclosure type 4x a Case Mounting 1 2 3 4 5 or 6 b Output Safe protection 1 2 3 or 4 c Optional modules shutdown 0 or 5 d Optional mechanical kit for digital position feedback 0 1 or 2 e Design varnish coding 1 ...

Page 56: ...evice by the user is not permitted Modifications to the device may only be performed by the manufacturer or an explosion protection specialist The splash guard cap must be screwed in place to achieve the IP 65 NEMA 4x protection class Operating the devices without the splash guard cap is prohibited The device may only be supplied with instrument air that is free of oil water and dust Do not use fl...

Page 57: ...safe circuit with max values Shutdown contact input Terminal 85 86 Ui 30 V Ci 3 7 nF Li negligibly small Mechanical digital feedback 2 Terminals Limit1 51 52 or Limit2 41 42 For max values see EC type examination test certificate number PTB 00 ATEX 2049 X 2 When using SJ2_S1N NO proximity switch the positioner may only be used at an ambient temperature range from 25 85 C 13 185 F Change from one t...

Page 58: ...80 C T6 40 C Tamb 65 C Change from one to two columns Special conditions for IECEx flameproof enclosures The positioner is designed for a maximum acceptable ambient temperature range between 40 85 C If the positioner is used at an ambient temperature above 60 C or below 20 C use cable entries and lines approved for a service temperature corresponding to the maximum ambient temperature increased by...

Page 59: ...al 51 52 or 85 86 Ui 30 V li 320 mA Pi 1 1 W Ci 3 7 nF Li negligibly small Change from one to two columns IECEx certification conditions operation as intrinsically safe equipment Special conditions relevant to the safe use of intrinsically safe positioners The local communication interface LKS for the TZIDC and the TZIDC 200 may only be operated at Um 30 V DC outside the potentially explosive area...

Page 60: ...ack 0 1 or 2 e Design varnish coding 1 or 2 f Device identification label 0 1 or 2 TZIDC 220 Positioner Model V18350 a012b3cd4ef XP I 2 CD T6 T5 T4 TA 82 C DIP II III 2 FG T6 T5 T4 Ta 82 C Enclosure type 4x a Case Mounting 1 2 3 4 5 or 6 b Output Safe protection 1 2 3 or 4 c Optional modules shutdown 0 or 5 d Optional mechanical kit for digital position feedback 0 1 or 2 e Design varnish coding 1 ...

Page 61: ...evice by the user is not permitted Modifications to the device may only be performed by the manufacturer or an explosion protection specialist The splash guard cap must be screwed in place to achieve the IP 65 NEMA 4x protection class Operating the devices without the splash guard cap is prohibited The device may only be supplied with instrument air that is free of oil water and dust Do not use fl...

Page 62: ...ircuit with max values Shutdown contact input Terminal 85 86 Ui 30 V Ci 3 7 nF Li negligibly small Mechanical digital feedback 2 Terminals Limit1 51 52 or Limit2 41 42 For max values see EC type examination test certificate number PTB 00 ATEX 2049 X 2 When using SJ2_S1N NO proximity switch the positioner may only be used at an ambient temperature range from 25 85 C 13 185 F Change from one to two ...

Page 63: ...80 C T6 40 C Tamb 65 C Change from one to two columns Special conditions for IECEx flameproof enclosures The positioner is designed for a maximum acceptable ambient temperature range between 40 85 C If the positioner is used at an ambient temperature above 60 C or below 20 C use cable entries and lines approved for a service temperature corresponding to the maximum ambient temperature increased by...

Page 64: ...0 V li 320 mA Pi 1 1 W Ci 3 7 nF Li negligibly small Change from one to two columns IECEx certification conditions operation as intrinsically safe equipment Special conditions relevant to the safe use of intrinsically safe positioners The local communication interface LKS for the TZIDC and the TZIDC 200 may only be operated at Um 30 V DC outside the potentially explosive area Special conditions fo...

Page 65: ...rectives EMC directive 2014 30 EU ATEX directive 2014 34 EU Explosion Protection Identification for intended use in potentially explosive atmospheres according to ATEX directive marking in addition to CE marking IEC standards FM Approvals US CSA International Canada IMPORTANT NOTE All documentation declarations of conformity and certificates are available in ABB s download area www abb com positio...

Page 66: ...ontact person Telephone Fax E mail Device details Type Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a threat or risk to health Yes No If yes which type of contamination please place an X next to the applicable items Biological Corrosive irritating Combustible highly extremely combustible Toxic Explosive Other toxic substan...

Page 67: ...Notes 42 18 85 EN TZIDC 200 TZIDC 210 TZIDC 220 67 Notes ...

Page 68: ... Fed Rep of Germany 04 2016 ABB 2016 42 18 85 EN Rev D 3KXE341008R4201 ABB Limited Process Automation Howard Road St Neots Cambridgeshire PE19 8EU UK Tel 44 0 870 600 6122 Fax 44 0 1480 213 339 Mail enquiries mp uk gb abb com ABB Inc Process Automation 125 E County Line Road Warminster PA 18974 USA Tel 1 215 674 6000 Fax 1 215 674 7183 ABB Automation Products GmbH Process Automation Schillerstr 72...

Reviews: