TLE Series 625 to 1000 PurePulse™ UL S2
UPS Installation Guide / REV-B
Fig. 4.4.1-8 TLE Series 1000 – UPS cabinet floor fixing points
Fig. 4.4.1-9 TLE Series 625 to 1000 – RPA Parallel System disposition
In case of Parallel System, try to place the UPS modules in sequence of their numbers (marked
on the packing).
If the units are positioned “side by side”, the side panels must be mounted on all units.
Remove the side air inlet grids on the intermediate units to run the control bus cable
connections.