TLE Series 625 to 1000 PurePulse™ UL S2
UPS Installation Guide / REV-B
TLE Series 625 to 1000
Power connection bus bars configuration for the top cable entry or bottom cable entry
The configuration of the TLE Series 625 to 1000 is with top cable entry as standard (see Fig. 4.9-3).
It is possible to configure the bus bars with bottom cable entry (see Fig. 4.9-4).
Fig. 4.9-3 TLE Series 625 to 1000 – Power connection configuration bus bars with top cable entry (standard)
Power connection cables are connected to bus bars using
M12 bolts
.
The bolts of the connection cables must be tightened with a torque wrench at
530 Lb-in / 60 Nm
.
Fig. 4.9-4 TLE Series 625 to 1000 - Power connection configuration bus bars with bottom cable entry