44/72
TLE Series 625 to 1000 PurePulse™ UL S2
UPS Installation Guide / REV-B
TLE Series 625 to 1000
PE-Ground connection bus bar configuration for the top cable entry or bottom cable entry
The configuration of the TLE Series 625 to 1000 is with top cable entry as standard.
It is possible to configure the bus bar with bottom cable entry (see Fig. 4.9-5).
Fig. 4.9-5 TLE Series 625 to 1000 – PE-Ground connection configuration bus bar with top or bottom cable entry
PE-Ground
connection cables
are connected to
bus bars using
M12
bolts
.
The bolts of the
connection cables
must be tightened
with a torque
wrench at
530 Lb-in
/ 60 Nm
.
TLE Series 625 to 1000
Battery connection bus bars configuration for the top cable entry or bottom cable entry
The configuration of the TLE Series 625 to 1000 is with top cable entry as standard.
It is possible to configure the bus bars with bottom cable entry (see Fig. 4.9-6).
Fig. 4.9-6 TLE Series 625 to 1000 – Battery connection configuration bus bars with top or bottom cable entry
Battery connection
cables are
connected to bus
bars using
M10
bolts
.
The bolts of the
connection cables
must be tightened
with a torque
wrench at
355 Lb-in
/ 40 Nm
.
TLES_UL_625-750
-1000_S2_UPS conn
ection PE_Top & Bo
ttom_01US
- +
1
2
Q1
0 OFF
I ON
- +
1
2
Q1
0 OFF
I ON
Position of the
PE-Ground bus bar
for cables input from
the top of the UPS
17.
72
"
450
mm
TLE Series 1000
TLE Series 625 & 750
Position of the
PE-Ground bus bar
for cables input from
the bottom of the UPS
TLES_UL_
625-1000
_S2_UPS c
onnection
PE_Top &
Bottom_A
BB_01US
Position of the bus bars for
cables input from the bottom of the UPS
TLES_UL_625-10
00_S2_UPS conn
ection battery_T
op & Bottom_AB
B_01US
Power Section cabinet
+
Position of the bus bars for
cables input from the top of the UPS
_
+
_
TLE Series 1000
TLE Series 625 & 750
Power Section cabinet