36/72
TLE Series 625 to 1000 PurePulse™ UL S2
UPS Installation Guide / REV-B
Fig. 4.8.3-3 Dual Input Utility Rectifier & Bypass
Fig. 4.8.3-4 Common Input Utility Rectifier & Bypass
Size of Branch Circuit Over Current Protection - All Models: - "CAUTION - To reduce the risk of fire, only connect
UPS to a circuit provided with (See below) maximum amperes branch circuit over current protection in
accordance with the NEC (National Electric Code), NSI / NFPA 70
UPS rating
F1 - AC Input Rectifier F2 - AC Input Bypass
F3 - AC Input
F4 - DC Input
80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
TLE Series 625
1200 A
1000 A
100
0 A
8
00 A
12
00 A
100
0 A
n/a
16
00 A
TLE Series 750
n/a
1200 A
12
00 A
10
00 A
n/a
12
00 A
n/a
2
000 A
TLE Series 1000
n/a
1600 A
16
00 A
n/a
n/a
16
00 A
n/a
2
5
00 A
Wiring!
Wire sizing according to
NEC Section 210-20 (a) Table 310-16
Use 167°F (75°C) copper or aluminum wire.
Wiring requirements:
AC Input Rectifier
3-Phase, 4 wire plus Ground
AC Input Bypass
3-Phase, 4 wire plus Ground
AC Output
3-Phase, 4 wire plus Ground
DC Input
2 wire (positive and negative) plus Ground.
Maximum recommended cable size
UPS rating
AC Input Rectifier AC Input Bypass
DC Input
AC Input
GND
TLE Series 625
5 x 500 kcmil
4 x 500 kcmil
6 x 500 kcmil
4 x 500 kcmil
1 x 4/0
TLE Series 750
5 x 500 kcmil
5 x 500 kcmil
8 x 500 kcmil
5 x 500 kcmil
1 x 250 kcmil
TLE Series 1000
6 x 500 kcmil
6 x 500 kcmil
10 x 500 kcmil
6 x 500 kcmil
1 x 350 kcmil