12  42/18-46-EN Rev. L | 

TEIP11, TEIP11-PS 

 

 

6.2

 

Electrical connections 

 

WARNING 

Risk of injury due to live parts! 

When the housing is open, contact protection is not provided 
and EMC protection is limited. 
Before opening the housing, switch off the power supply. 

 

NOTICE 

For electrical installation, the following standards, data, and 
documents must be complied with: 
—  The applicable regulations and safety standards for the 

installation and operation of electrical systems. 

—  The additional regulations, standards, and directives for 

the installation and operation of explosion-proof 
systems, if explosion-proof devices are in use. 

—  The values for the electrical connection (see section 

"Electrical data" on page 12). 

—  The information on the explosion protection certificate, 

for an explosion-proof design. 

 

NOTICE 

Adverse effect on input signals 

Power supply leads in the immediate vicinity of the signal 
lines produce interference which can impair the input signals 
to the devices. 
Do not install the signal line together with power supply 
leads. 

 

6.2.1

 

Cable glands 

The field mount housings feature a Pg 11 cable entry. 
 

Aluminum or stainless steel field mount housing 

 

Ex Protection

 

Cable entry 

Standard / Ex ia 

Cable gland 1/2" NPT 

Ex d 

Tapped bore M20 x 1.5 

FM / CSA "Intrinsically Safe" / 

"Explosion Proof" 

Tapped bore 1/2" NPT 

 

 

6.2.2

 

Position of the terminals 

The electrical connection is provided by 2-pin screw terminals 
for conductor cross-sections up to a maximum of 2.5 mm

2

 

(14 AWG). 
Do not reverse the polarity (+/-) when connecting the signal 
line. 

 

Control room housing unit for rail and block mounting 

The terminals are located on the side of the housing unit. 
 

Plastic, aluminum, or stainless steel field mount housing 

The terminals are located inside the housing unit. Therefore, 
the field mount housing must be opened in order to connect 
the cable. 
 

6.2.3

 

Electrical data 

Signal range 

0 ... 20 mA or 4 ... 20 mA 
0 ... 10 mA or 10 ... 20 mA 
4 ... 12 mA or 12 ... 20 mA 
(additional ranges available upon request) 
 

Input resistance 

Ri = 260 Ω at 20 °C (68 °F), Tk + 0.4 %/K 
 

Overload limit 

30 mA (for explosion-proof devices, see the information in 
chapter "Use in potentially explosive atmospheres" on page 5) 
 

Capacitance/inductance 

Negligible 
 

6.3

 

Pneumatic connections 

 

NOTICE 

Damage to components! 

Always blow dust, splinters, and any other dirt particles off 
the air inlet line before it is connected. Such particles could 
block the unit. 
Take precautions to ensure that in the event of an error the 
pressure does not rise above 4 bar (60 psi). This could result 
in mechanical damage to the unit. 

 

NOTICE 

—  The TEIP11 and TEIP11-PS I/P signal converters may 

only be operated with instrument air that is free of oil, 
water, and dust. 

—  If a version with a plastic housing is operated with 

combustible gas, an additional line must be installed to 
route the gas to a safe place in the open air. 

 
1/8, 1/4, and 3/8 NPT threaded holes are provided for 
connecting the air pipes (supply air and output pipes). 
The connections for the power supply (supply air) and the 
output are marked accordingly. 
 

Summary of Contents for TEIP11

Page 1: ...Operating Instruction 42 18 46 EN Rev L TEIP11 TEIP11 PS I P signal converter...

Page 2: ...ional documentation on TEIP11 TEIP11 PS is available for download free of charge at www abb com positioners Alternatively simply scan this code Manufacturer ABB Automation Products GmbH Measurement An...

Page 3: ...nting 8 3 2 2 Control room housing unit for block mounting 8 3 2 3 Field mount housing 8 4 Product identification 9 4 1 Name plate 9 4 2 Scope of delivery 9 4 2 1 Accessories 9 5 Transport and storage...

Page 4: ...al word WARNING indicates an imminent danger Failure to observe this information may result in death or severe injury CAUTION The signal word CAUTION indicates an imminent danger Failure to observe th...

Page 5: ...that corresponds to the minimum ambient temperature Versions with an intrinsically safe control head may no longer be operated as intrinsically safe if they have been previously operated with the fla...

Page 6: ...xplosion if the device is operated with the housing or terminal box open Before opening the housing or the terminal box note the following points Check that a valid fire permit is available Make sure...

Page 7: ...signal flowing through the coil A counterforce is applied on the other side of the lever arm through the dynamic air pressure present at the nozzle and the flapper The force is controlled in such a w...

Page 8: ...nit for block mounting enables you to install a number of converters in a small space This design features central air supply via connection block and stop valves in the air connectors of the integrat...

Page 9: ...sport documents All claims for damages must be submitted to the shipper without delay and before installation 5 2 Storage conditions Bear the following points in mind when storing devices Store the de...

Page 10: ...ls that are mounted in a horizontal position the electrical connection for the device should preferably be facing up 6 1 2 Control room housing unit for block mounting For this design a special connec...

Page 11: ...steel field mount housing 1 Terminal for signal input covered 2 Cable entry 3 Supply air connection 4 Output covered Installation instructions Position the housing so that the cable gland is facing d...

Page 12: ...onductor cross sections up to a maximum of 2 5 mm2 14 AWG Do not reverse the polarity when connecting the signal line Control room housing unit for rail and block mounting The terminals are located on...

Page 13: ...i 1 Output signal 0 2 1 bar 3 15 psi 0 4 2 bar 6 30 psi 1 1 Only valid for option 509 increased input signal Air consumption 0 2 kg h 0 16 Nm3 h 0 1 scfm 7 Commissioning Once the installation is compl...

Page 14: ...acc to page 2 for nearest service location 10 Recycling and disposal 10 1 Disposal NOTICE Products that are marked with this symbol may not be disposed of through municipal garbage collection points...

Page 15: ...ls Company Address Contact person Telephone Fax E Mail Device details Typ Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a thr...

Page 16: ...16 42 18 46 EN Rev L TEIP11 TEIP11 PS 12 1 Control Document 12 1 1 Connection diagram 900842 FM...

Page 17: ...TEIP11 TEIP11 PS 42 18 46 EN Rev L 17...

Page 18: ...18 42 18 46 EN Rev L TEIP11 TEIP11 PS 12 1 2 Connection diagram 900842 CSA...

Page 19: ...TEIP11 TEIP11 PS 42 18 46 EN Rev L 19...

Page 20: ...positioners Note We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB do...

Reviews: