TEIP11, TEIP11-PS
| 42/18-46-EN Rev. L 13
6.3.1
Pneumatic data TEIP11
Instrument air
Free of oil, water, and dust acc. to DIN/ISO 8573-1
Pollution and oil content according to Class 3
Pressure dew point 10 K below operating temperature
Supply pressure
1.4 ... 10 bar (20 ... 145 psi)
Output signal
0,2 ... 1 bar (3 ... 15 psi)
Air consumption
Equivalent to air capacity
6.3.2
Pneumatic data TEIP11-PS
Instrument air
Free of oil, water, and dust acc. to DIN/ISO 8573-1
Pollution and oil content according to Class 3
Pressure dew point 10 K below operating temperature
Supply pressure
1,4 bar (20 psi)
2,5 bar (36 psi)
1
Output signal
0,2 ... 1 bar (3 ... 15 psi)
0,4 ... 2 bar (6 ... 30 psi)
1
1 Only valid for option 509 - increased input signal
Air consumption
0.2 kg/h = 0.16 Nm
3
/h = 0.1 scfm
7
Commissioning
Once the installation is complete and the electrical and
pneumatic components are connected, the I/P signal
converter is ready to use. No further adjustment is required.
8
Maintenance
The I/P signal converters are adjusted prior to delivery.
After an extensive operating time the signal conversion may
exceed the tolerance limits due to aging or drift.
If the tolerance limits are exceeded, this can be corrected
through adjustment.
Two adjustment screws are used for the adjustment process.
NOTICE
When using a field mount housing first remove the cover to
access the screws.
Fig. 9:
Adjustment screws
1
Span
2
Zero point