4.3.4
Configuring Profibus DP
The configuration of the Profibus is carried out using two DECIMAL switches. The switch
on the left is x10 and that on the right x1.
The device has to be restarted each time the configuration is changed (switch auxiliary
voltage off and on again).
If the SYNCHROTACT 5 device is the first or last component on the bus, the termination
switch must be set to ON in order to prevent reflections on the bus line. However, if an
external termination plug is used, the termination switch must remain OFF.
Selecting the slave address
The address can be set between 0-99 using the DECIMAL switches described above.
The left-hand switch determines the tens position and the switch on the right the units
position.
Selecting the Baudrate:
The Baudrate is determined by the master and automatically recognised by the
SYNCHROTACT 5. The following Baudrates are supported:
9,6 kbit/s
19,2 kbit/s
93,75 kbit/s
187,5 kbit/s
500 kbit/s
1,5 Mbit/s
3 Mbit/s
6 Mbit/s
12 Mbit/s
Note
1
4
3
2
6
5
9
8
7
ON
7
8
0
6
9 1
4
5
3
2
7
8
0
6
9 1
4
5
3
2
Connector
Termination
Switch
DECIMAL
Switch
x10
DEZIMAL
Switch
x1
LEDs
Note