10 Technical
data
10.1 Inputs
Auxiliary voltage
Nominal voltage range
24 to 250 VDC
100 to 230 VAC
Permissible voltage range
18 to 300 VDC
75 to 300 VAC
Power consumption READY
OPERATING
<12 W/<18 VA
<12 W/<18 VA
Measuring inputs U1, U2
Nominal voltage range
50 to 130 VAC
Voltage range
0 to 130 % Un
Nominal frequency
16
2
/
3
or 50/60 Hz
Frequency range
10 to 100 Hz
Maximum power consumption per channel
<10 mVA
Digital inputs
Nominal voltages
24/48 VDC
Current consumption
6 to 8 mA
Minimum voltage for logic 1
18 VDC
Relay inputs from SYN 5500
Coil nominal voltage
24 VDC
Operate voltage
18 VDC
Release voltage
3,6 VDC
Coil resistance
1152
Coil inductivity
1000 mH
10.2 Outputs
Paralleling relay and relays from SYN 5500
Maximum contact voltage
250 VAC/VDC
Limiting breaking capacity
6 A
Limiting continuous current
10 A
Limiting making capacity
20 A
Maximum switching power ON AC/DC
1500 VA/W
Maximum switching power OFF AC/DC (resistive)
1500/150 VA/W
Adjusting command and signaling relays
Maximum contact voltage
250 VAC/VDC
Limiting continuous current
1.5 AAC/ADC
Maximum switching power ON/OFF AC/DC
50 VA/W
Auxiliary voltage output for digital inputs
Maximum output power
4 W