Parameter sets 1 to 7
1. Actual value calibration “Calibrate act values“
No.
Parameter name
Symbol
Range/resolution
Unit
Default setting of all
parameter sets
1.
Nominal voltage
Un
50 to 130
VAC
110
2. Nominal
frequency
fn
16
2
/
3
, 50, 60
Hz
50
3. Voltage
tuning
UOffset
12.0
% 0
4. Angle
tuning
Offset
180
DEG 0
2. Command generation “Paralleling cmd gen“
No.
Parameter name
Symbol
Range/resolution
Unit
Default setting of parameter
sets
1 to 6
7
1.
Test function
TEST ton
ON/OFF
-
OFF
OFF
2.
Paralleling time
t on
0 to 990/10
ms
100
100
3.
Paralleling command duration
tp on
OFF, 10 to 990/10
ms
990
OFF
4.
Monitoring time
t supervis
0 to 99
s
10
10
5.
Multiple commands
MULTIPLE CMD
ON/OFF
-
OFF
OFF
3. Paralleling conditions “Parallel conditions“
No.
Parameter name
Symbol
Range/resolution
Unit
Default setting of parameter
sets
1 to 6
7
1.
Slip limit, oversynchronous
-smax
0.00 to 6.00
%
0.4
0.2
2.
Slip limit, sub-synchronous
+smax
0.00 to 6.00
%
0.4
0.2
3.
Angle limit, negative
-
max
0 to 99
DEG
10
10
4.
Angle limit, positive
+
max
0 to 99
DEG
10
10
5.
Max. voltage difference, overexcited
-
Umax
0 to 40
%
3
3
6.
Max. voltage difference, underexcited
+
Umax
0 to 40
%
3
3
7.
Maximum voltage
Umax
105 to 130
%
120
120
8.
Minimum voltage
Umin
50 to 95
%
80
80
4. “Dead bus conditions“
No.
Parameter name
Symbol
Range/resolution
Unit
Default setting of all
parameter sets
1.
Maximum zero voltage
U0max
0 to 49
%
5
2.
Release U1 = no-voltage
U1not
ON/OFF
-
OFF
3.
Release U2 = no-voltage
U2not
ON/OFF
-
OFF
4.
Release for U1 and U2 = no-voltage
1*2not ON/OFF -
OFF
5. “Voltage matcher“
No.
Parameter name
Symbol
Range/resolution
Unit
Default setting of parameter
sets
1 to 6
7
1.
Test function
TEST U-Match
ON/OFF
-
OFF
OFF
2.
Voltage adjustment characteristic
dU/dt
0.00 to 5.00
%/s
0.30
0.00
3.
Pulse interval
ts U
1 to 20
s
2
2
4.
Minimum pulse duration
tp Umin
0.05 to 2.00
s
0.05
0.05
5.
Switchover to variable intervals
INVERSE U
ON/OFF
-
OFF
OFF
6.
Switchover to tap changer
TAP CHANGER
ON/OFF
-
OFF
OFF
6. “Frequency matcher“
No.
Parameter name
Symbol
Range/resolution
Unit
Default setting of parameter
sets
1 to 6
7
1.
Test function
TEST f-Match
ON/OFF
-
OFF
OFF
2.
Frequency adjustment characteristic
df/dt
0.00 to 5.00
%/s
0.20
0.00
3.
Pulse interval
ts f
1 to 120
s
20
20
4.
Minimum pulse duration
tp fmin
0.05 to 2.00
s
0.05
0.05
5.
Switchover to variable intervals
INVERSE f
ON/OFF
-
OFF
OFF
7. “General parameters“
No.
Parameter name
Symbol
Range/resolution
Unit
Default setting of all
parameter sets
1.
Blocking time after selection
t block
1 to 10
s
2
2.
Total paralleling time
t tot
OFF, 0.5 to 15/
Steps: 0.5
min 5