68
SCU200
INSITE ENERGY MANAGEMENT SYSTEM
//”type”: online or historical
“type”: “online”,
“values”: {
// object_id: [variables]
“415”: [“currentTrms”, “currentAc”, “currentDc”],
“389”: [“voltageL1”]
},
//”begin_timestamp”: only for historical
“begin_timestamp”: 1663231649,
//”end_timestamp”: only for historical
“end_timestamp”: 1663318059,
//”resolution”: only for historical, possible values ‘30s’, ‘15min’, ‘1h’, ‘1d’,
‘1m’, maximum date range is 1000 samples per period (or 12 for 1m)
“resolution”: “1h”
}
]
}
Online values e.g.
{
“data”: [
{
“type”: “online”,
“values”: {
“415”: [“currentTrms”, “currentAc”, “currentDc”],
“389”: [“voltageL1”]
}
}
]
}
Response:
{
“id”: “scu200hs”,
“ip”: “192.168.1.200”,
“data”: [
{
“timestamp”: 1669794027,
“values”: {
“389”: {
“voltageL1”: 243.9
},
“415”: {
“currentTrms”: 0.11,
“currentAc”: 0.07,
“currentDc”: 0.08