51
SCU200
INSITE ENERGY MANAGEMENT SYSTEM
6.5.My plant
6.5.1.Site plan view
6.5.2.Groups
This page allows you to create or remove groups of devices. By clicking on “Add new group”, it is possible
to create a new group by selecting the type of devices.
Once a group type has been selected, it is required to type the name of the group and add a description.
For each group it is possible to associate one or more items. One device can be assigned to multiple
groups.
By clicking on the pencil icon “Edit” it is possible to edit all the fields of the selected group. By clicking on
checkbox and then on button “Remove”, the selected groups will be deleted.
The values from devices in one group are summed by tags (for Modbus RTU/TCP devices tags can be
configured per register) and they can be presented on dashboard widget or in historical values.
6.5.3.Devices
For each added device the status is presented as dot indicator colors with proper tooltip
●
Green
Device is assigned/configured and fully operational
●
Red
Device is unassigned or not responding
●
Orange
Device is assigned and operational, but only partially responding, it
might be caused by device not fully responded for all expected values
in time or for the sensors by removing device from which Voltage
or PF source was previously selected. In this situation only electric
current is being measured
●
Gray
Waiting for first data from device
The Modbus ID pool for Current sensors, I/O modules, INS-S/H, MOD & AR is 1-32. The maximum no.
those devices connected is 32 (I/O module count as 4 devices).
The Modbus ID pool for Modbus RTU devices is 33-48.
The Modbus ID pool for Wireless M-Bus modules is 49-64