27
10
3
8,8
74
SCU200
INSITE ENERGY MANAGEMENT SYSTEM
3.3.5.Smart auxiliary and signal contact
Technical feature
Unit
Description SSD
Supply voltage
[VDC]
Supplied by the InSite modular bus
Connection
InSite modular bus
Power loss
[W]
0,1
Mounting Position
Right
Pluggable accessories
S2CHR (x2)
S2C-S/HR (x2)
Suitable for Product Class
Miniature Circuit Breaker
Residual Current Device
Arc Fault Detetcions Devices
Suitable For
MCBs S200 series, S300P
RCDs F200, DS201
AFDDs S-ARC1, DS-ARC1
Switch disconnectors SD200
Mounting method
35mm DIN rail (DIN 5022)
Degree of protection
IP20
Dimensions
[mm]
8.8x103x74 (0.5M)
Weight
[g]
30
Operating temperature
[°C]
-25... +60
Storage temperature
[°C]
-40... +85
Operating altitude
[m]
0… 2000
Standards
IEC61010-1
IEC 61326-1
IEC 60068
IEC / EN 62019 for Main functionality
IEC 60947-5-1 for Main functionality
IEC61009 for RCDs compatibility
EN 60898-1 for MCBs compatibility
3.3.6.Smart auxiliary and signal contact allow to:
• Read contacts status of the MCCBs, MCBs or RCDs connected and communicate through flat cable.
• Detect change of status (trip indication) of the MCCBs, MCBs or RCDs connected and communicate
through flat cable.
• Measure internal temperature of the MCCBs, MCBs or RCDs connected and communicate through flat
cable.