16.7 Troubleshooting
The following table collects up a series of typical service situations, which are useful in order to understand and solve hypothetical faults or
malfunctions.
N.B.:
1. Before consulting the following table, check any lighting up of the LEDs located on the front of the unit for some seconds.
2. FN Indicates normal operation of the PR 113.
3. In the case where the suggestions proposed do not lead to a solution of the problem, please contact the ABB SACE service assistance.
N° Situation
Possible causes
Suggestions
1
There is no serial communication activity
1. Incorrect cabling of the connections.
1. Check the connections
with the remote supervision system
2. There is no auxiliary voltage
2. Recover the auxiliary voltage
3. Incorrect communication parameters
3. Set the correct parameters
2
Incorrect indication of the power circuit breaker status,
Incorrect cabling of the connections
Check the connections
power circuit breaker position and state of the springs
3
Impossible to send power circuit breaker
1. Incorrect cabling of the connections
1. Check the connections
opening and/or closing controls
2. No power supply to the opening
2. Recover the power
and/or closing coils
supply voltage
4
Impossible to change the PR113 parameters
The unit is set to Remote
Set the unit to Local
and/or carry out opening/closing
controls from the front keyboard
5
Impossible to change the PR113 parameters
1. The unit is set to Local
1. Set the unit to Remote
and/or send remote
2. The device is a PR113/PD-A
2. FN
opening/closing controls
6
“No Int. Bus Comm” message on the display
No communication activity between
Contact ABB SACE
protection unit and communication
unit inside the PR113
7
No updating of the opening data
Vaux not present during the trip
FN
16.8 Warning and error messages
All the messages which can be shown on the display relating to incorrect configurations, generic alarms or linked to useful information are described
below.
Incorrect configurations
MESSAGE
DESCRIPTION
MODBUS not config.
The dialogue unit does not have the address set (ABB default setting)
V_AUX OFF: Comm. OFF
The communication bus is not operating because there is no auxiliary voltage.
NO Int. Bus Comm.
No communication between the protection unit and the dialogue unit inside the PR112/PD.
NOT available
The function required is not available.
CB Status Unknown
See par.16.4.4.3
MODBUS Wink
The Wink mode has been activated. In this condition, rear illumination of the display is intermittent.
16.9 Accessories
See paragraph 15.7.