10
INSTRUCTION HANDBOOK
6.2 PHASE 2 – SLIDING CONTACTS BLOCK
Actions to be performed
Tools
Torx key
No. 8
No. 30
Pliers
Flat screwdriver (x2)
Cutter
17
By means of the torx key (size 30) unscrew the
2 + 2 screws fixing the 2 side walls located at
both sides of the sliding contacts block to the
circuit breaker main structure.
20
Manually remove the base and the cover.
19
Move the sliding contacts block as shown in
the picture and by means of the torx key (size
8) unscrew the 6 screws fixing the base and
the cover.
18
Manually remove the 2 side walls located on
the sides of the sliding contact block.