54
INSTRUCTION HANDBOOK
UL version - Current rating up to 1600A
Tools
Torx key
No. 15
No. 40
207
By means of the torx key (size 15) unscrew the
4 screws fixing the claw contacts to the pole.
209
Manually remove the spacers located below the
claw contacts.
210
By means of the torx key (size 40) unscrew
the 4 screws fixing the terminals and their
protections to the pole.
208
Push the claw contacts as indicated by the arrows
and after manually remove the claw contacts.
Circuit breakers in UL version characterized by a current rating up to 1600A show differences
at level of parts involved in this disassembly phase, consequently here below an analogous