109
Table 5.1.18.-1 IRF codes
Fault code
Type of fault
4
Error in output relay PO1
5
Error in output relay PO2
6
Error in output relay PO3
7
Error in output relay SO1
8
Error in output relay SO2
9
Error in the enable signal for output relay PO1, PO2, SO1 or
SO2
10, 11, 12
Error in the feedback, enable signal or output relay PO1, PO2,
SO1 or SO2
13
Error in optional output relay SO3
14
Error in optional output relay SO4
15
Error in optional output relay SO5
16
Error in the enable signal for optional output relay SO3, SO4 or
SO5
17, 18, 19
Error in the feedback, enable signal or optional output relay
SO3, SO4 or SO5
20, 21
Auxiliary voltage dip
30
Faulty program memory
50, 59
Faulty work memory
51, 52, 53
a)
, 54, 56
Faulty parameter memory
b)
55
Faulty parameter memory, calibration parameters
80
Optional I/O module missing
81
Optional I/O module unknown
82
Optional I/O module configuration error
85
Power supply module faulty
86
Power supply module unknown
90
Hardware configuration error
95
Communication module unknown
104
Faulty configuration set (for IEC 60870-5-103)
131, 139, 195, 203,
222, 223
Internal reference voltage error
253
Error in the measuring unit
a)
Can be corrected by restoring factory settings for CPU.
b)
All settings will be zero during the fault.
For further information on internal relay faults, refer to the Operator
’
s
Manual.
Warnings
In case of a warning, the relay continues to operate except for those protection
functions possibly affected by the fault, and the green target LED (ready)
remains lit as during normal operation. Further, a fault target message, which