Channel 1
Table 5.1.17.1.-5 Event codes E1...E16
Channel
Event
Description
Weight-
ing
factor
Default
value
1
E1
Pickup signal from element 59P-1
activated
1
1
1
E2
Pickup signal from element 59P-1 reset
2
0
1
E3
Trip signal from element 59P-1 activated
4
1
1
E4
Trip signal from element 59P-1 reset
8
0
1
E5
Pickup signal from element 59P-2 or 47
activated
16
1
1
E6
Pickup signal from element 59P-2 or 47
reset
32
0
1
E7
Trip signal from element 59P-2 or 47
activated
64
1
1
E8
Trip signal from element 59P-2 or 47
reset
128
0
1
E9
Pickup signal from element 27P-1
activated
256
1
1
E10
Pickup signal from element 27P-1 reset
512
0
1
E11
Trip signal from element 27P-1 activated
1024
1
1
E12
Trip signal from element 27P-1 reset
2048
0
1
E13
Pickup signal from element 27P-2 or 27D
activated
4096
1
1
E14
Pickup signal from element 27P-2 or 27D
reset
8192
0
1
E15
Trip signal from element 27P-2 or 27D
activated
16384
1
1
E16
Trip signal from 27P-2 or 27D reset
32768
0
Default value of event mask 1V155
21845
Table 5.1.17.1.-6 Event codes E17...E24
Channel
Event
Description
Weight-
ing
factor
Default
value
1
E17
Pickup signal from element 59N-1
activated
1
1
1
E18
Pickup signal from element 59N-1 reset
2
0
1
E19
Trip signal from element 59N-1 activated
4
1
1
E20
Trip signal from element 59N-2 reset
8
0
1
E21
Pickup signal from element 59N-2
activated
16
1
1
E22
Pickup signal from element 59N-2 reset
32
0
106
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972
Summary of Contents for REU 610
Page 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 10: ...10 ...
Page 128: ...128 ...
Page 138: ......
Page 139: ......