Table 5.1.17.-3 Recorded data: Channels 1...5 (Continued)
Recorded data
Event (R)
Value
n Channel 1
n-1 Channel 2 n-2 Channel 3 n-3 Channel 4 n-4 Channel 5
Pickup duration of
element 59N-2
1V15
2V15
3V15
4V15
5V15
0
…
100%
Pickup duration of
external trip
1V16
2V16
3V16
4V16
5V16
0/100%
Time stamp of the
recorded data, date
1V17
2V17
3V17
4V17
5V17
YY-MM-DD
Time stamp of the
recorded data, time
1V18
2V18
3V18
4V18
5V18
HH.MM;SS.sss
a)
If
is not based on negative phase-sequence voltage U
2
, dashes are shown on the LCD and "999" when read via serial
communication.
b)
If is not based on positive phase-sequence voltage U
1
, dashes are shown on the LCD and "999" when read via serial communication.
Disturbance recorder
Table 5.1.17.-4 Parameters for the disturbance recorder
Description
Parameter (channel 0)
R, W
Value
Remote triggering
M1
a)
W
1
Clear recorder memory
M2
W
1
Sampling rate
M15
b)
R, W
800/960 Hz
400/480 Hz
50/60 Hz
Station identification/unit number
M18
R, W
0...9999
Rated frequency
M19
R
50 or 60 Hz
Name of the station
M20
R, W
Max 16 characters
Digital channel texts
M40...M47
R
-
Analog channel texts
M60...M63
R
-
Analog channel conversion factor and unit
for primary voltage transformer(s)
M80
c)d)
R, W
Factor 0.00...600, unit
(V, kV), e.g. 20.0,kV
M81 and
R
M82
R
Analog channel conversion factor and unit
for residual voltage U
n
M83
c)
R, W
Factor 0.00...600, unit
(V, kV), e.g. 20.0,kV
Internal trigger signals' checksum
V236
R, W
0...4095
Internal trigger signal's edge
V237
R, W
0...4095
Checksum of internal signal storing mask V238
b)
R, W
0...4095
Post-triggering recording length
V240
R, W
0...100%
External trigger signal's checksum
V241
R, W
0...31
94
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972
Summary of Contents for REU 610
Page 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 10: ...10 ...
Page 128: ...128 ...
Page 138: ......
Page 139: ......